Skip to the content.

MPC Integration for NeqSim Process Systems

This document describes the Model Predictive Control (MPC) integration package for NeqSim, which bridges the gap between rigorous process simulation and advanced control systems.

Overview

The neqsim.process.mpc package provides seamless integration between NeqSim’s thermodynamic process simulation (ProcessSystem) and Model Predictive Control. It enables:

Architecture

┌─────────────────────────────────────────────────────────────────────────────┐
│                           ProcessLinkedMPC                                   │
│       (High-level bridge between ProcessSystem and MPC)                      │
├─────────────────────────────────────────────────────────────────────────────┤
│                                                                              │
│  ┌─────────────┐  ┌─────────────┐  ┌─────────────┐  ┌─────────────┐         │
│  │ Manipulated │  │ Controlled  │  │ Disturbance │  │    State    │         │
│  │  Variable   │  │  Variable   │  │  Variable   │  │  Variable   │         │
│  │    (MV)     │  │    (CV)     │  │    (DV)     │  │   (SVR)     │         │
│  └──────┬──────┘  └──────┬──────┘  └──────┬──────┘  └──────┬──────┘         │
│         │                │                │                │                 │
│         └────────────────┴────────────────┴────────────────┘                 │
│                                    │                                         │
│         ┌──────────────────────────┼──────────────────────────┐              │
│         ▼                          ▼                          ▼              │
│  ┌─────────────────┐  ┌─────────────────────────┐  ┌─────────────────┐      │
│  │ ProcessLinear-  │  │    StepResponse-        │  │   Nonlinear-    │      │
│  │     izer        │  │      Generator          │  │   Predictor     │      │
│  └────────┬────────┘  └───────────┬─────────────┘  └────────┬────────┘      │
│           │                       │                          │               │
│           └───────────────────────┼──────────────────────────┘               │
│                                   ▼                                          │
│                    ┌───────────────────────────┐                             │
│                    │   LinearizationResult     │                             │
│                    │  (Gain matrices + OP)     │                             │
│                    └─────────────┬─────────────┘                             │
│                                  │                                           │
│  ┌───────────────────────────────┼───────────────────────────────┐           │
│  │                               │                               │           │
│  ▼                               ▼                               ▼           │
│ ┌──────────────┐  ┌────────────────────────┐  ┌────────────────────┐        │
│ │ StateSpace-  │  │ IndustrialMPC-         │  │   SubrModl-        │        │
│ │  Exporter    │  │   Exporter             │  │    Exporter        │        │
│ │(JSON/MATLAB) │  │(Step Response/Config)  │  │ (Nonlinear Model)  │        │
│ └──────────────┘  └────────────────────────┘  └────────────────────┘        │
│                               │                                              │
│  ┌────────────────────────────┴────────────────────────────┐                 │
│  │                                                         │                 │
│  ▼                                                         ▼                 │
│ ┌─────────────────────────┐               ┌─────────────────────────┐       │
│ │ ControllerDataExchange  │               │   SoftSensorExporter    │       │
│ │   (Real-time PCS I/O)   │               │  (Estimator Configs)    │       │
│ └─────────────────────────┘               └─────────────────────────┘       │
│                                                                              │
└──────────────────────────────────┬───────────────────────────────────────────┘
                                   │
                                   ▼
                        ┌─────────────────────┐
                        │   ProcessSystem     │
                        │  (NeqSim Simulation)│
                        └─────────────────────┘

Quick Start

Basic MPC Setup

import neqsim.process.mpc.*;
import neqsim.process.processmodel.ProcessSystem;
import neqsim.process.equipment.separator.Separator;
import neqsim.process.equipment.stream.Stream;
import neqsim.process.equipment.valve.ThrottlingValve;
import neqsim.thermo.system.SystemSrkEos;

// Create fluid
SystemInterface fluid = new SystemSrkEos(298.15, 50.0);
fluid.addComponent("methane", 0.8);
fluid.addComponent("ethane", 0.15);
fluid.addComponent("propane", 0.05);
fluid.setMixingRule("classic");

// Build process
ProcessSystem process = new ProcessSystem();

Stream feed = new Stream("feed", fluid);
feed.setFlowRate(1000.0, "kg/hr");
feed.setTemperature(25.0, "C");
feed.setPressure(50.0, "bara");

ThrottlingValve valve = new ThrottlingValve("inlet_valve", feed);
valve.setOutletPressure(30.0);

Separator separator = new Separator("separator", valve.getOutletStream());

process.add(feed);
process.add(valve);
process.add(separator);
process.run();

// Create linked MPC
ProcessLinkedMPC mpc = new ProcessLinkedMPC("pressureController", process);

// Define variables
mpc.addMV("inlet_valve", "opening", 0.0, 1.0);  // Valve opening 0-100%
mpc.addCV("separator", "pressure", 30.0);        // Control to 30 bar

// Identify the local steady-gain model
mpc.identifyModel(60.0);

// Control loop
for (int step = 0; step < 100; step++) {
    double[] moves = mpc.step();
    System.out.printf("Step %d: MV=%.3f CV=%.2f%n",
        step, moves[0], mpc.getCurrentCVs()[0]);
}

Variable Types

Manipulated Variables (MVs)

MVs are process inputs that the controller can adjust:

// Create MV with basic bounds
ManipulatedVariable mv = mpc.addMV("valve", "opening", 0.0, 1.0);

// Create MV with rate limit
ManipulatedVariable mv2 = mpc.addMV("heater", "duty", 0.0, 1000.0, 100.0);
// Rate limit: max 100 kW change per sample

// Set move suppression cost
mpc.setMoveSuppressionWeight("valve.opening", 0.5);

Supported MV Properties:

Controlled Variables (CVs)

CVs are process outputs that we want to control:

// Setpoint control
ControlledVariable cv = mpc.addCV("separator", "pressure", 30.0);
cv.setWeight(1.0);  // CV priority

// Zone control (CV only needs to stay within bounds)
ControlledVariable cv2 = mpc.addCVZone("separator", "liquidLevel", 30.0, 70.0);

// Hard constraints
mpc.setConstraint("separator", "pressure", 25.0, 35.0);

Supported CV Properties:

Disturbance Variables (DVs)

DVs are measured but uncontrolled disturbances for feedforward:

DisturbanceVariable dv = mpc.addDV("feed", "flowRate");

Model Identification

Linearization Method

Fast identification using finite differences:

mpc.identifyModel(60.0);  // 60 second sample time

// Access results
LinearizationResult result = mpc.getLinearizationResult();
double[][] gains = result.getGainMatrix();
double gain = result.getGain("separator.pressure", "valve.opening");

Step Response Method

More accurate for highly nonlinear processes:

mpc.identifyModelFromStepTests(
    60.0,    // Sample time (seconds)
    600.0,   // Test duration per step (seconds)
    5.0      // Step size (% of range)
);

Direct Linearizer Access

For more control over the identification process:

ProcessLinearizer linearizer = new ProcessLinearizer(process);
linearizer.setRelativePerturbation(0.01);  // 1% perturbation
linearizer.setUseCentralDifference(true);

// Add variables
linearizer.addMV(new ManipulatedVariable("valve.opening", valve, "opening"));
linearizer.addCV(new ControlledVariable("sep.pressure", separator, "pressure"));

// Linearize
LinearizationResult result = linearizer.linearize();

// Check linearity
boolean isLinear = linearizer.checkLinearity(0.05);  // 5% tolerance

Model Export

Export models for external MPC systems:

StateSpaceExporter exporter = mpc.exportModel();

// Generate discrete state-space model
StateSpaceExporter.StateSpaceModel model = exporter.toDiscreteStateSpace(60.0);

// Export to JSON (for Python)
exporter.exportJSON("process_model.json");

// Export to MATLAB
exporter.exportMATLAB("process_model.m");

// Export to CSV
exporter.exportCSV("model_");  // Creates model_A.csv, model_B.csv, etc.

JSON Format

{
  "sampleTime": 60.0,
  "sampleTimeUnit": "seconds",
  "numStates": 2,
  "numInputs": 1,
  "numOutputs": 2,
  "inputNames": ["valve.opening"],
  "outputNames": ["separator.pressure", "separator.liquidLevel"],
  "A": [[0.95, 0.0], [0.0, 0.98]],
  "B": [[0.5], [0.1]],
  "C": [[1.0, 0.0], [0.0, 1.0]],
  "D": [[0.0], [0.0]]
}

MATLAB Format

% NeqSim State-Space Model Export
A = [0.95 0.0; 0.0 0.98];
B = [0.5; 0.1];
C = [1.0 0.0; 0.0 1.0];
D = [0.0; 0.0];
Ts = 60.0;

sys = ss(A, B, C, D, Ts);
sys.InputName = {'valve.opening'};
sys.OutputName = {'separator.pressure', 'separator.liquidLevel'};

Nonlinear Prediction

Use NonlinearPredictor to evaluate a specified input trajectory with process simulation. ProcessLinkedMPC.calculate() uses the local gain model by default. Supplying sampled step responses selects its linear horizon optimizer, as shown in the export/injection example below.

Direct Predictor Access

NonlinearPredictor predictor = new NonlinearPredictor(process, 60.0, 20);

// Add variables
predictor.addMV(new ManipulatedVariable("valve.opening", valve, "opening"));
predictor.addCV(new ControlledVariable("sep.pressure", separator, "pressure"));

// Create trajectory
NonlinearPredictor.MVTrajectory trajectory = new NonlinearPredictor.MVTrajectory();
double[] valveTrajectory = new double[20];
Arrays.fill(valveTrajectory, 0.6);  // Constant 60% opening
trajectory.addMV("valve.opening", valveTrajectory);

// Predict
NonlinearPredictor.PredictionResult result = predictor.predict(trajectory);
double[] pressurePrediction = result.getCVTrajectory("separator.pressure");

Advanced Features

Model Updating

Enable automatic model updates during operation:

mpc.setModelUpdateInterval(100);  // Re-linearize every 100 steps

Constraint Handling

// CV hard constraints (must be satisfied)
ControlledVariable cv = mpc.getControlledVariables().get(0);
cv.setHardConstraints(true);
cv.setMinValue(25.0);
cv.setMaxValue(35.0);

// CV soft constraints (penalty-based)
cv.setHardConstraints(false);
cv.setConstraintViolationCost(100.0);

Zone Control

// CV only penalized when outside zone
ControlledVariable cv = mpc.addCVZone("tank", "level", 30.0, 70.0);
// Controller only acts when level leaves 30-70% zone

Step Response Generator

For detailed model identification:

StepResponseGenerator generator = new StepResponseGenerator(process);

// Add variables
generator.addMV(mv);
generator.addCV(cv);

// Configure
generator.setStepDuration(600.0);     // 10 minutes per test
generator.setStepSize(0.05);          // 5% steps
generator.setSampleInterval(10.0);    // 10 second samples
generator.setBidirectional(true);     // Test both directions

// Generate all responses
StepResponseGenerator.StepResponseMatrix matrix = generator.generateAllResponses();

// Access individual responses
StepResponse response = matrix.get("separator.pressure", "valve.opening");
double gain = response.getGain();
double timeConstant = response.getTimeConstant();
double deadTime = response.getDeadTime();

// Export for DMC
StateSpaceExporter exporter = new StateSpaceExporter(matrix);
exporter.exportStepCoefficients("dmc_model.csv", 60);

Integration with AI Platforms

The MPC integration package is designed for seamless integration with AI/ML platforms:

Python Integration via neqsim-python

import jpype
import neqsim

# Access MPC classes
ProcessLinkedMPC = jpype.JClass('neqsim.process.mpc.ProcessLinkedMPC')
StateSpaceExporter = jpype.JClass('neqsim.process.mpc.StateSpaceExporter')

# Create MPC (assuming process is already set up)
mpc = ProcessLinkedMPC("controller", process)
mpc.addMV("valve", "opening", 0.0, 1.0)
mpc.addCV("separator", "pressure", 30.0)
mpc.identifyModel(60.0)

# Export model
exporter = mpc.exportModel()
exporter.exportJSON("model.json")

# Load in Python for custom optimization
import json
with open("model.json") as f:
    model = json.load(f)

A = np.array(model['A'])
B = np.array(model['B'])
# Use with scipy.signal, python-control, or custom MPC

Real-Time Control Loop

// Configure for real-time
mpc.setSampleTime(1.0);  // 1 second
mpc.setPredictionHorizon(60);
mpc.setControlHorizon(10);
mpc.identifyModel(1.0);

// Real-time loop
ScheduledExecutorService executor = Executors.newSingleThreadScheduledExecutor();
executor.scheduleAtFixedRate(() -> {
    try {
        // Read current measurements (from OPC, etc.)
        updateProcessMeasurements(process);

        // Calculate and apply control
        mpc.step();

        // Write outputs (to OPC, etc.)
        writeProcessOutputs(mpc.getLastMoves());
    } catch (Exception e) {
        logger.error("Control error", e);
    }
}, 0, 1000, TimeUnit.MILLISECONDS);

Best Practices

  1. Start with linearization - Use identifyModel() first; only switch to step response testing if needed for accuracy.

  2. Check linearity - Use ProcessLinearizer.checkLinearity() to validate the linearization accuracy.

  3. Conservative tuning - Start with larger prediction horizons and move suppression weights, then tighten.

  4. Model updates - Enable periodic re-linearization for processes with significant nonlinearity.

  5. Constraint margins - Leave margin between operational constraints and safety limits.

  6. Test in simulation - Validate controller behavior thoroughly before connecting to real equipment.

Package Structure

neqsim/process/mpc/
├── package-info.java           # Package documentation
├── MPCVariable.java            # Base class for MPC variables
├── ManipulatedVariable.java    # Manipulated variable (MV)
├── ControlledVariable.java     # Controlled variable (CV)
├── DisturbanceVariable.java    # Disturbance variable (DV)
├── StateVariable.java          # State variable (SVR) for nonlinear MPC
├── ProcessLinearizer.java      # Automatic Jacobian calculation
├── LinearizationResult.java    # Gain matrices container
├── StepResponse.java           # Single MV-CV step response
├── StepResponseGenerator.java  # Automated step testing
├── NonlinearPredictor.java     # Full simulation prediction
├── StateSpaceExporter.java     # Model export (JSON/CSV/MATLAB)
├── ProcessLinkedMPC.java       # Main bridge class
├── IndustrialMPCExporter.java  # Step response & config export for industrial MPC
├── ControllerDataExchange.java # Real-time data exchange interface
├── SoftSensorExporter.java     # Soft-sensor/estimator configurations
└── SubrModlExporter.java       # Nonlinear model export (SubrModl format)

Industrial Control System Integration

The MPC package includes comprehensive support for integration with industrial MPC platforms.

Step Response Model Export

Export models in formats compatible with industrial MPC systems:

IndustrialMPCExporter exporter = mpc.createIndustrialExporter();
exporter.setTagPrefix("UNIT1.separator");
exporter.setApplicationName("GasProcessing");

// Export step response coefficients in CSV format
exporter.exportStepResponseCSV("step_responses.csv");

// Export gain matrix
exporter.exportGainMatrix("gains.csv");

// Export complete object structure for configuration
exporter.exportObjectStructure("controller_config.json");

// Export comprehensive configuration with all model data
exporter.exportComprehensiveConfiguration("mpc_config.json");

Real-Time Data Exchange

Interface with Process Control Systems (PCS) using standardized data exchange:

ControllerDataExchange exchange = mpc.createDataExchange();
exchange.setTagPrefix("UNIT1.MPC");

// Control loop with external controller
while (running) {
    // Update inputs from process measurements
    exchange.updateInputs(mvValues, cvValues, dvValues);
    exchange.updateSetpoints(setpoints);
    exchange.updateLimits(cvLowLimits, cvHighLimits, mvLowLimits, mvHighLimits);

    // Execute and get outputs
    exchange.execute();
    ControllerDataExchange.ControllerOutput output = exchange.getOutputs();

    // Check quality and status
    if (output.getStatus() == ControllerDataExchange.ExecutionStatus.SUCCESS) {
        applyMVs(output.getMvTargets());
    }
}

Quality Flags:

Execution Status:

Soft Sensor Export

Export soft-sensor configurations for industrial calculation engines:

SoftSensorExporter softExporter = new SoftSensorExporter(process);
softExporter.setTagPrefix("UNIT1");
softExporter.setApplicationName("GasProcessing");

// Add sensors for thermodynamic properties
softExporter.addDensitySensor("sep_gas_density", "separator", "gas outlet");
softExporter.addViscositySensor("sep_oil_visc", "separator", "oil outlet");
softExporter.addPhaseFractionSensor("sep_gas_frac", "separator");
softExporter.addCompositionEstimator("sep_comp", "separator", "gas outlet",
    new String[]{"methane", "ethane", "propane"});

// Export in JSON and CVT formats
softExporter.exportConfiguration("soft_sensors.json");
softExporter.exportCVTFormat("soft_sensors.cvt");

Nonlinear MPC with State Variables

For nonlinear MPC systems that use programmed model objects:

// Create MPC with state variables
ProcessLinkedMPC mpc = new ProcessLinkedMPC("wellController", process);
mpc.addMV("choke", "opening", 0.0, 1.0);
mpc.addCV("well", "pressure", 50.0);
mpc.addDV("reservoir", "pressure");

// Add state variables (SVR) for internal model states
StateVariable flowIn = mpc.addSVR("well", "flowIn", "qin");
StateVariable flowOut = mpc.addSVR("well", "flowOut", "qout");
mpc.addSVR("choke", "cv", "cv");

// Configure bias handling for state estimation
flowIn.setBiasTfilt(30.0);   // 30 second filter on bias
flowIn.setBiasTpred(120.0);  // 2 minute prediction decay

// Export for nonlinear MPC system
SubrModlExporter exporter = mpc.createSubrModlExporter();
exporter.setModelName("WellModel");
exporter.addParameter("Volume", 100.0, "m3");
exporter.addParameter("Height", 2000.0, "m");
exporter.addParameter("Density", 700.0, "kg/m3");
exporter.addParameter("Compressibility", 500.0, "bar");
exporter.addParameter("ProductionIndex", 8.0, "m3/h/bar");

// Export configuration files
exporter.exportConfiguration("well_config.txt");
exporter.exportMPCConfiguration("mpc_config.txt", true); // true = SQP solver
exporter.exportIndexTable("well_ixid.cpp");
exporter.exportJSON("well_model.json");

Generated Configuration Example:

WellModelProc:    NonlinearSQP
         Volume=  100
         Height=  2000
        Density=  700
Compressibility=  500
ProductionIndex=  8

  SubrXvr:       Pdownhole
         Text1=  "Downhole pressure"
         Text2=  ""
         DtaIx=  "pdh"
          Init=  147.7

  SubrXvr:       Pwellhead
         Text1=  "Wellhead pressure"
         Text2=  ""
         DtaIx=  "pwh"
          Init=  10.4

MPC Configuration Parameters:

Parameter Description Typical Value
SteadySolver Steady-state solver type SQP or QP
IterOpt Enable iterative optimization ON/OFF
IterNewSens Recalculate sensitivities each iteration ON/OFF
IterQpMax Maximum QP iterations 10
IterLineMax Maximum line search iterations 10
LinErrorLim Linearization error limit 0.2
MajItLim Major iteration limit (SQP) 200
FuncPrec Function precision 1e-08
FeTol Constraint feasibility tolerance 1e-03
OptimTol Optimality tolerance 1e-05

Export versus injection with a scheduled takeaway reduction

The executable export/injection example routes 100 kg/h of methane through a NeqSim splitter. A local response model represents the effect of third-stage suction pressure on the split. At 48 bara, injection takes 20 kg/h. Raising suction by 1 bar diverts another 2 kg/h from export to injection. The assumed export-header pressure rises by 0.5 bar for each kg/h by which export exceeds the takeaway nomination. These synthetic gains describe this example only. A compressor application needs identified responses, valve limits and anti-surge protection appropriate to the equipment.

Every 15 s the controller predicts the next six minutes, optimizes four independent suction settings and holds the fourth setting for the rest of the horizon. It applies the first setting. Suction is limited to 48–54 bara and can move by 1 bar per scan. A preferred setting of 48 bara favours export. A soft upper limit of 100 bara on the header discourages routing more gas to export than the receiving system can take.

At 60 s, takeaway drops from 80 to 74 kg/h. With advance notice, the controller diverts some gas to injection before the change. The test checks the cost in diverted gas and compares the integrated pressure exceedance with a pressure-feedback controller subject to the same actuator limits. At 135 s an unexpected drop to 64 kg/h puts the measured header pressure 5 bar above the one-step forecast. Even at the suction upper limit, export is at least 68 kg/h, so the next scan must report at least 2 bar of upper slack. The test checks the measured export-plus-injection balance and the applied first move on every scan.

Quantity in the synthetic replay Preview MPC Pressure feedback
Additional gas injected before the planned reduction, relative to feedback 0.0215 kg 0 kg
Integrated pressure above 100 bara during the five planned-reduction scans 12.55 bar·s 90.00 bar·s

The first scan after detecting the surprise reports 4.143 bar of upper slack. The 1 bar-per-scan slew limit prevents the controller from immediately reaching the maximum suction pressure.

See Also