NeqSim Industrial MPC Integration Guide

This document describes how NeqSim thermodynamic and process simulation capabilities can be integrated with industrial Model Predictive Control (MPC) systems for real-time optimization and production optimization.

Table of Contents

  1. Overview
  2. Integration Architecture
  3. Model Generation Workflow
  4. Integration Patterns
  5. Production Optimization
  6. Bottleneck Analysis and Resolution
  7. Soft Sensor Integration
  8. Gain Scheduling
  9. Model Validation
  10. Implementation Examples

Overview

The Complementary Roles

NeqSim and industrial MPC systems serve complementary roles in process control and optimization:

Aspect NeqSim Industrial MPC
Primary Function Rigorous thermodynamic calculations Real-time control execution
Execution Time Seconds to minutes Milliseconds
Model Type First-principles, nonlinear Linear/simplified nonlinear
Usage Offline analysis, model generation Online control, optimization
Accuracy High-fidelity physics Operational accuracy

Integration Benefits


Integration Architecture

┌─────────────────────────────────────────────────────────────────────────┐
│                        ENGINEERING WORKSTATION                          │
│  ┌─────────────────┐    ┌──────────────────┐    ┌──────────────────┐   │
│  │   NeqSim        │───▶│  Model Export    │───▶│  MPC Config      │   │
│  │   Process       │    │  (Step Response, │    │  Files           │   │
│  │   Simulation    │    │   SubrModl, etc) │    │                  │   │
│  └─────────────────┘    └──────────────────┘    └────────┬─────────┘   │
└───────────────────────────────────────────────────────────┼─────────────┘
                                                            │
                    ┌───────────────────────────────────────▼─────────────┐
                    │              INDUSTRIAL MPC SYSTEM                  │
                    │  ┌─────────────────────────────────────────────┐   │
                    │  │              MPC Controller                  │   │
                    │  │  ┌──────────┐  ┌──────────┐  ┌───────────┐  │   │
                    │  │  │ Linear   │  │ Nonlinear│  │ Production│  │   │
                    │  │  │ MPC      │  │ MPC      │  │ Optimizer │  │   │
                    │  │  │ (ExprModl│  │ (SubrModl│  │           │  │   │
                    │  │  │  style)  │  │  style)  │  │           │  │   │
                    │  │  └──────────┘  └──────────┘  └───────────┘  │   │
                    │  └─────────────────────────────────────────────┘   │
                    │                         │                          │
                    │  ┌─────────────────────▼───────────────────────┐   │
                    │  │            Soft Sensors / Estimators         │   │
                    │  │  (Property tables, correlations from NeqSim) │   │
                    │  └──────────────────────────────────────────────┘   │
                    └─────────────────────────────────────────────────────┘
                                              │
                    ┌─────────────────────────▼─────────────────────────┐
                    │                 PROCESS CONTROL SYSTEM            │
                    │           (DCS / PLC / Safety Systems)            │
                    └───────────────────────────────────────────────────┘
                                              │
                    ┌─────────────────────────▼─────────────────────────┐
                    │                    PROCESS PLANT                   │
                    │  (Separators, Compressors, Heat Exchangers, etc)  │
                    └───────────────────────────────────────────────────┘

Model Generation Workflow

The fragments below use the imports and equipment names in the complete example. Run them inside a method accepting String outputDirectory and declaring throws Exception for file export. These examples identify steady-state gains. The exporter’s first-order time constant is an explicit assumption; validate dynamics and dead time against plant data or a transient model before using the model for control. Declaring a disturbance variable does not identify its gains: ProcessLinearizer uses the sensitivities supplied by setCvSensitivity.

Step 1: Build NeqSim Process Model

Path output = Files.createDirectories(Paths.get(outputDirectory));
SystemInterface fluid = new SystemSrkEos(298.15, 50.0);
fluid.addComponent("methane", 0.80);
fluid.addComponent("ethane", 0.10);
fluid.addComponent("propane", 0.05);
fluid.addComponent("n-butane", 0.03);
fluid.addComponent("n-pentane", 0.02);
fluid.setMixingRule("classic");

ProcessSystem process = new ProcessSystem();
Stream feed = new Stream("Feed", fluid);
feed.setFlowRate(500.0, "kg/hr");
Separator separator = new Separator("HP Separator", feed);
separator.setInternalDiameter(1.5);
StreamInterface gasProduct = separator.getGasOutStream();
gasProduct.setName("Gas Product");
process.add(feed);
process.add(separator);
process.add(gasProduct); // Register the outlet so the MPC can resolve it by name.
process.run();

Step 2: Configure MPC Variables

ProcessLinkedMPC mpc = new ProcessLinkedMPC("HP_Separator_MPC", process);

// Bounds and setpoints use the units configured on each variable.
mpc.addMV("Feed", "flowRate", 200.0, 800.0).setUnit("kg/hr");
mpc.addMV("Feed", "pressure", 30.0, 70.0).setUnit("bara");
mpc.addCVZone("Gas Product", "flowRate", 100.0, 600.0).setUnit("kg/hr");
mpc.addCVZone("Gas Product", "pressure", 45.0, 55.0).setUnit("bara");
mpc.setConstraint("Gas Product", "flowRate", 0.0, 650.0);
mpc.setConstraint("Gas Product", "pressure", 30.0, 70.0);

DisturbanceVariable feedTemperature = mpc.addDV("Feed", "temperature");
feedTemperature.setUnit("K");

addMV, addCV, and addDV take the name of a registered process unit. Set the unit on the returned variable. The current bound-variable readers support stream flow, pressure, and temperature; they do not read arbitrary separator level or component-fraction properties. A level-control model needs an appropriate dynamic inventory model and measurement/control integration.

Step 3: Generate Step Response Models

mpc.setPredictionHorizon(30);
mpc.setControlHorizon(10);
mpc.identifyModel(10.0); // Sample interval in seconds; identifies steady-state gains.
if (!mpc.getLinearizationResult().isSuccessful()) {
    throw new IllegalStateException(mpc.getLinearizationResult().getErrorMessage());
}

IndustrialMPCExporter exporter = mpc.createIndustrialExporter();
exporter.setDefaultTimeConstant(60.0); // Assumed first-order dynamics, in seconds.
exporter.exportStepResponseModel(output.resolve("separator_mpc_model.json").toString());
exporter.exportStepResponseCSV(output.resolve("separator_mpc_model.csv").toString());
exporter.exportComprehensiveConfiguration(output.resolve("separator_mpc_config.json").toString());

exportStepResponseModel writes JSON; use exportStepResponseCSV for CSV.


Integration Patterns

Pattern 1: Offline Model Generation → Online Execution

The most common integration pattern where NeqSim generates models offline that are executed in real-time by the industrial MPC.

┌─────────────────┐     Model Files      ┌──────────────────┐
│     NeqSim      │ ─────────────────▶  │  Industrial MPC   │
│ (Engineering)   │  CSV, JSON, Config  │  (Real-time)      │
└─────────────────┘                      └──────────────────┘
     Offline                                   Online
   (minutes)                               (milliseconds)

Use Cases:

Pattern 2: Property Table Lookup

Build a table explicitly by solving the thermodynamic system at each grid point. The example writes bulk mixture density and specific enthalpy; a phase-specific sensor must also record phase identity and handle phase appearance or disappearance. Add java.io.BufferedWriter, java.nio.charset.StandardCharsets, java.nio.file.Files, java.nio.file.Paths, and java.util.Locale to the imports.

try (BufferedWriter writer = Files.newBufferedWriter(output.resolve("property_table.csv"),
        StandardCharsets.UTF_8)) {
    writer.write("pressure_bara,temperature_K,density_kg_m3,enthalpy_J_kg");
    writer.newLine();
    for (double pressure : new double[] {20.0, 50.0, 80.0}) {
        for (double temperature : new double[] {280.0, 300.0, 320.0}) {
            SystemInterface sample = fluid.clone();
            sample.setPressure(pressure, "bara");
            sample.setTemperature(temperature, "K");
            new ThermodynamicOperations(sample).TPflash();
            sample.initProperties();
            writer.write(String.format(Locale.ROOT, "%.1f,%.1f,%.8g,%.8g",
                pressure, temperature, sample.getDensity("kg/m3"),
                sample.getEnthalpy("J/kg")));
            writer.newLine();
        }
    }
}

Validate interpolation errors, phase boundaries, composition, and grid coverage before using a table online. SoftSensorExporter exports sensor definitions; it does not calculate a lookup table or fit property correlations.

Pattern 3: Gain Scheduling

Different operating regions require different model gains. NeqSim calculates models at multiple operating points.

double[] pressures = {35.0, 50.0, 65.0}; // bara, inside the 30-70 bara MV bounds
double[] temperatures = {280.0, 300.0, 320.0}; // K
double basePressure = feed.getPressure("bara");
double baseTemperature = feed.getTemperature("K");
try {
    for (double pressure : pressures) {
        for (double temperature : temperatures) {
            feed.setPressure(pressure, "bara");
            feed.setTemperature(temperature, "K");
            process.run();
            mpc.identifyModel(10.0);
            String filename = String.format(Locale.ROOT, "model_P%.0f_T%.0f.csv", pressure, temperature);
            exporter.exportStepResponseCSV(output.resolve(filename).toString());
        }
    }
} finally {
    feed.setPressure(basePressure, "bara");
    feed.setTemperature(baseTemperature, "K");
    process.run();
    mpc.identifyModel(10.0);
}

The industrial MPC selects the appropriate model based on current operating conditions.

Pattern 4: Nonlinear MPC with Steady-State Solver

SubrModlExporter writes model configuration and variable mappings. An external runtime still needs the nonlinear calculation and a plant-specific adapter; a configuration file alone does not supply an executable controller.

StateVariable gasFlowState = mpc.addSVR("Gas Product", "flowRate", "gas_flow");
gasFlowState.setUnit("kg/hr");
gasFlowState.setModelValue(gasProduct.getFlowRate("kg/hr"));

SubrModlExporter subrModl = mpc.createSubrModlExporter();
subrModl.setModelName("HP_Separator_NL");
subrModl.exportConfiguration(output.resolve("separator_subrmodl.cnf").toString());
subrModl.exportMPCConfiguration(output.resolve("separator_smpc.cnf").toString(), true);
subrModl.exportJSON(output.resolve("separator_subrmodl.json").toString());

Refresh state model values explicitly when the process is rerun. StateVariable stores model and measured values; setting a property name does not implement a new dynamic state or an automatic measurement connection.


Production Optimization

Overview

Industrial MPC systems excel at production optimization - maximizing throughput while respecting all process constraints. NeqSim provides the physics-based models that enable accurate constraint handling.

Optimization Hierarchy

┌─────────────────────────────────────────────────────────────────┐
│                    PRODUCTION OPTIMIZATION                       │
│                    (Economic Objective)                          │
│         Maximize: Revenue - Operating Costs                      │
└─────────────────────────────────────────────────────────────────┘
                              │
                              ▼
┌─────────────────────────────────────────────────────────────────┐
│                    INDUSTRIAL MPC                                │
│                    (Constraint Handling)                         │
│         Subject to: Equipment limits, Quality specs,            │
│                     Safety constraints, Environmental           │
└─────────────────────────────────────────────────────────────────┘
                              │
                              ▼
┌─────────────────────────────────────────────────────────────────┐
│                    NEQSIM MODELS                                 │
│                    (Physical Constraints)                        │
│         Provides: Thermodynamic limits, Phase boundaries,       │
│                   Property calculations, Equipment models       │
└─────────────────────────────────────────────────────────────────┘

Optimization Variables

The industrial MPC optimizes by pushing the process toward constraints while maintaining stability:

Variable Type NeqSim Contribution MPC Usage
Throughput Maximum flow capacity Maximize within limits
Quality Composition calculations Constraint satisfaction
Energy Enthalpy, heat duties Cost minimization
Efficiency Compressor curves, pump efficiency Optimal setpoints

Example: Separator Train Optimization

Use ProductionOptimizer for a steady-state throughput target, as shown in Production Optimization Setup. Supply equipment limits from the installed design and evaluate their physical meaning at the current operating point. For example:

double gasVelocity = separator.getGasSuperficialVelocity(); // m/s
double allowableGasVelocity = separator.getMaxAllowableGasVelocity(); // m/s
if (!Double.isFinite(allowableGasVelocity) || allowableGasVelocity <= 0.0) {
    throw new IllegalStateException("A valid separator capacity basis is required");
}
boolean gasVelocityWithinLimit = gasVelocity <= allowableGasVelocity;

// Illustrative installed gas mass-rate limit, independently specified in kg/hr.
// This configures an existing CV; it does not convert velocity into mass flow.
mpc.setConstraint("Gas Product", "flowRate", 0.0, 650.0);
exporter.exportVariableConfiguration(output.resolve("separator_constraints.json").toString());

These checks do not establish liquid carryover or residence-time acceptance. Those constraints need vessel geometry, inventories, and a selected separation model. getMaxAllowableGasVelocity uses the configured design K-factor and assumes a liquid density of 1000 kg/m³ when no liquid phase is present; review that assumption for sizing.


Bottleneck Analysis and Resolution

What is Bottleneck Analysis?

Bottleneck analysis identifies which constraints are limiting production and quantifies the value of relaxing each constraint.

NeqSim’s Role in Bottleneck Analysis

  1. Equipment Capacity Modeling
    • Separator flooding velocity
    • Compressor surge/choke limits
    • Heat exchanger duty limits
    • Pump cavitation limits
  2. Thermodynamic Constraints
    • Phase envelope boundaries
    • Hydrate formation curves
    • Dew point specifications
    • Flash point limits
  3. Quality Specifications
    • Composition targets
    • Water content limits
    • H2S specifications
    • Heating value requirements

Bottleneck Resolution Workflow

┌─────────────────────────────────────────────────────────────────┐
│   Step 1: IDENTIFY ACTIVE CONSTRAINTS                            │
│   Industrial MPC reports which constraints are limiting          │
│   production (shadow prices / Lagrange multipliers)              │
└─────────────────────────────────────────────────────────────────┘
                              │
                              ▼
┌─────────────────────────────────────────────────────────────────┐
│   Step 2: ANALYZE WITH NEQSIM                                    │
│   Use rigorous simulation to understand constraint physics:      │
│   - What causes the limit?                                       │
│   - How sensitive is it to operating conditions?                 │
│   - What would happen if constraint is violated?                 │
└─────────────────────────────────────────────────────────────────┘
                              │
                              ▼
┌─────────────────────────────────────────────────────────────────┐
│   Step 3: EVALUATE DEBOTTLENECKING OPTIONS                       │
│   NeqSim simulates "what-if" scenarios:                          │
│   - Increase equipment size                                      │
│   - Change operating pressure                                    │
│   - Add parallel equipment                                       │
│   - Modify feed conditions                                       │
└─────────────────────────────────────────────────────────────────┘
                              │
                              ▼
┌─────────────────────────────────────────────────────────────────┐
│   Step 4: UPDATE MPC MODELS                                      │
│   After physical changes, regenerate models with NeqSim          │
│   and deploy updated MPC configuration                           │
└─────────────────────────────────────────────────────────────────┘

Example: Compressor Bottleneck

This fragment requires a solved compressor named Export_Compressor with a loaded performance map. Add Compressor and CompressorChartInterface from neqsim.process.equipment.compressor to the imports.

Compressor compressor = (Compressor) process.getUnit("Export_Compressor");
CompressorChartInterface chart = compressor.getCompressorChart();
double surgeLimit = chart.getSurgeFlowAtSpeed(compressor.getSpeed());
double chokeLimit = chart.getStoneWallFlowAtSpeed(compressor.getSpeed());
double currentFlow = compressor.getInletStream().getFlowRate("m3/hr");
if (!Double.isFinite(surgeLimit) || !Double.isFinite(chokeLimit)
        || surgeLimit <= 0.0 || chokeLimit <= surgeLimit) {
    throw new IllegalStateException("Load valid surge and stonewall map data first");
}
double surgeMargin = 100.0 * (currentFlow - surgeLimit) / surgeLimit;
double chokeMargin = 100.0 * (chokeLimit - currentFlow) / chokeLimit;
logger.info("Surge margin: {}%; choke margin: {}%", surgeMargin, chokeMargin);

The flow basis is actual inlet m³/h, matching the map; do not compare map flow with kg/h. To investigate higher inlet pressure or cooler gas, change the upstream feed or cooler, rerun the process, and recalculate both limits and margins. Changing only a downstream inlet stream can be overwritten by the upstream calculation.

Bottleneck Value Calculation

The industrial MPC calculates the economic value (shadow price) of each constraint:

Constraint Shadow Price Interpretation
Compressor Power $500/MW Each additional MW enables $500/hr more production
Separator Pressure $100/bar Relaxing pressure by 1 bar gains $100/hr
Export Quality $200/ppm Each ppm H2S relaxation worth $200/hr

NeqSim can validate these shadow prices by simulating the actual production gain when constraints are relaxed.


Soft Sensor Integration

Phase Properties

ThermodynamicOperations thermoOps = new ThermodynamicOperations(fluid);
thermoOps.TPflash();
fluid.initProperties();

if (fluid.hasPhaseType("gas")) {
    double gasCompressibility = fluid.getPhase("gas").getZ();
    double gasViscosity = fluid.getPhase("gas").getViscosity("cP");
    logger.info("Gas Z: {}; viscosity: {} cP", gasCompressibility, gasViscosity);
}
if (fluid.hasPhaseType("oil")) {
    logger.info("Liquid density: {} kg/m3", fluid.getPhase("oil").getDensity("kg/m3"));
}
if (fluid.hasPhaseType("gas") && fluid.hasPhaseType("oil")) {
    int gasPhase = fluid.getPhaseNumberOfPhase("gas");
    int oilPhase = fluid.getPhaseNumberOfPhase("oil");
    double surfaceTension = fluid.getInterphaseProperties()
        .getSurfaceTension(gasPhase, oilPhase, "mN/m");
    logger.info("Gas/oil surface tension: {} mN/m", surfaceTension);
}

Molecular Weight Estimation

SoftSensorExporter softSensor = exporter.createSoftSensorExporter();
softSensor.addMolecularWeightSensor("Gas_MW", "Gas Product");
softSensor.addDensitySensor("Gas_Density", "Gas Product", "kg/m3");
softSensor.exportConfiguration(output.resolve("gas_soft_sensors.json").toString());

The export describes inputs, units, and equipment mappings. Calculate the values from the current process state, or develop and validate a lookup/correlation separately.

Heating Value Calculation

Add neqsim.standards.gasquality.Standard_ISO6976_2016 to the imports. Heating values are calculated by a gas-quality standard, not by methods on a phase.

if (!fluid.hasPhaseType("gas")) {
    throw new IllegalStateException("A gas phase is required for gas sales properties");
}
SystemInterface salesGas = fluid.phaseToSystem("gas");
Standard_ISO6976_2016 gasQuality = new Standard_ISO6976_2016(salesGas, 15.0, 15.0, "volume");
gasQuality.calculate();
double gcv = gasQuality.getValue("SuperiorCalorificValue"); // kJ/m3 at reference conditions
double ncv = gasQuality.getValue("InferiorCalorificValue"); // kJ/m3 at reference conditions
double wobbeIndex = gasQuality.getValue("SuperiorWobbeIndex"); // kJ/m3

This example uses 15 °C for the volume and combustion reference temperatures; select the reference conditions required by the sales contract.


Gain Scheduling

Operating Point Identification

String[] operatingNames = {"Low_Rate", "Normal", "High_Rate"};
// Columns: mass flow (kg/hr), pressure (bara), temperature (K).
double[][] operatingPoints = {
    {250.0, 40.0, 290.0},
    {500.0, 50.0, 300.0},
    {750.0, 60.0, 310.0}
};
double originalFlow = feed.getFlowRate("kg/hr");
double originalPressure = feed.getPressure("bara");
double originalTemperature = feed.getTemperature("K");
try {
    for (int point = 0; point < operatingPoints.length; point++) {
        feed.setFlowRate(operatingPoints[point][0], "kg/hr");
        feed.setPressure(operatingPoints[point][1], "bara");
        feed.setTemperature(operatingPoints[point][2], "K");
        process.run();
        mpc.identifyModel(10.0);
        exporter.exportStepResponseCSV(output.resolve("model_" + operatingNames[point] + ".csv").toString());
    }
} finally {
    feed.setFlowRate(originalFlow, "kg/hr");
    feed.setPressure(originalPressure, "bara");
    feed.setTemperature(originalTemperature, "K");
    process.run();
    mpc.identifyModel(10.0);
}

Keep each operating point and its linearization perturbations inside the MV bounds. Recalculate disturbance sensitivities at each point when using feedforward control.

Model Selection Logic

The industrial MPC uses operating conditions to select the appropriate model:

IF (flow < 375 kg/hr) THEN
    USE model_Low_Rate
ELSE IF (flow < 625 kg/hr) THEN
    USE model_Normal
ELSE
    USE model_High_Rate

Model Validation

Continuous Model Monitoring

The surrounding application must apply measured conditions, supply MPC predictions, and decide acceptable error limits. The following helper compares already ordered outputs and uses an explicit tolerance per output, in that output’s engineering unit.

public class ModelValidator {
    public static boolean withinTolerance(double[] simulated, double[] predicted,
            double[] tolerances) {
        if (simulated.length != predicted.length || simulated.length != tolerances.length) {
            throw new IllegalArgumentException("Output and tolerance dimensions must match");
        }
        for (int index = 0; index < simulated.length; index++) {
            if (!Double.isFinite(simulated[index]) || !Double.isFinite(predicted[index])
                    || !Double.isFinite(tolerances[index]) || tolerances[index] < 0.0
                    || Math.abs(simulated[index] - predicted[index]) > tolerances[index]) {
                return false;
            }
        }
        return true;
    }
}

Bias Detection

StateVariable gasFlowBias = new StateVariable("Gas_Flow", gasProduct, "flowRate");
gasFlowBias.setUnit("kg/hr");
gasFlowBias.setModelValue(gasProduct.getFlowRate("kg/hr"));
gasFlowBias.setBiasTfilt(0.0); // Unfiltered residual for this example.
// Synthetic measurement for demonstration; replace with a timestamp-aligned plant value.
gasFlowBias.setMeasuredValue(gasProduct.getFlowRate("kg/hr") + 5.0);
logger.info("Gas flow measurement-minus-model bias: {} kg/hr", gasFlowBias.getBias());

Update the model and measured values explicitly for each comparison. Filtering and prediction settings require separate tuning and verification of their update cadence.


Implementation Examples

Complete Separator Control Example

Save as SeparatorMPCIntegration.java and run with an optional output directory argument (default mpc-output). The example identifies flow/pressure gains, exports model and sensor configuration files, and returns the configured MPC for reuse. It does not execute a closed-loop level controller. The first-order time constant of 60 s is an illustrative export assumption, not an identified separator response.

import java.nio.file.Files;
import java.nio.file.Path;
import java.nio.file.Paths;
import org.apache.logging.log4j.LogManager;
import org.apache.logging.log4j.Logger;
import neqsim.process.equipment.separator.Separator;
import neqsim.process.equipment.stream.Stream;
import neqsim.process.equipment.stream.StreamInterface;
import neqsim.process.mpc.DisturbanceVariable;
import neqsim.process.mpc.IndustrialMPCExporter;
import neqsim.process.mpc.ProcessDerivativeCalculator;
import neqsim.process.mpc.ProcessLinkedMPC;
import neqsim.process.mpc.SoftSensorExporter;
import neqsim.process.mpc.StateVariable;
import neqsim.process.mpc.SubrModlExporter;
import neqsim.process.processmodel.ProcessSystem;
import neqsim.thermo.system.SystemInterface;
import neqsim.thermo.system.SystemSrkEos;
import neqsim.thermodynamicoperations.ThermodynamicOperations;

public class SeparatorMPCIntegration {
    private static final Logger logger = LogManager.getLogger(SeparatorMPCIntegration.class);

    public static ProcessLinkedMPC configureAndExport(String outputDirectory) throws Exception {
        Path output = Files.createDirectories(Paths.get(outputDirectory));
        SystemInterface fluid = new SystemSrkEos(298.15, 50.0);
        fluid.addComponent("methane", 0.80);
        fluid.addComponent("ethane", 0.10);
        fluid.addComponent("propane", 0.05);
        fluid.addComponent("n-butane", 0.03);
        fluid.addComponent("n-pentane", 0.02);
        fluid.setMixingRule("classic");

        ProcessSystem process = new ProcessSystem();
        Stream feed = new Stream("Feed", fluid);
        feed.setFlowRate(500.0, "kg/hr");
        Separator separator = new Separator("HP Separator", feed);
        separator.setInternalDiameter(1.5);
        StreamInterface gasProduct = separator.getGasOutStream();
        gasProduct.setName("Gas Product");
        process.add(feed);
        process.add(separator);
        process.add(gasProduct);
        process.run();

        ProcessLinkedMPC mpc = new ProcessLinkedMPC("HP_Sep_MPC", process);
        mpc.addMV("Feed", "flowRate", 200.0, 800.0).setUnit("kg/hr");
        mpc.addMV("Feed", "pressure", 30.0, 70.0).setUnit("bara");
        mpc.addCVZone("Gas Product", "flowRate", 100.0, 600.0).setUnit("kg/hr");
        mpc.addCVZone("Gas Product", "pressure", 45.0, 55.0).setUnit("bara");
        mpc.setConstraint("Gas Product", "flowRate", 0.0, 650.0);
        mpc.setConstraint("Gas Product", "pressure", 30.0, 70.0);

        // Identify the temperature disturbance's steady-state sensitivities explicitly.
        ProcessDerivativeCalculator derivative = new ProcessDerivativeCalculator(process);
        derivative.addInputVariable("Feed.temperature", "K");
        derivative.addOutputVariable("Gas Product.flowRate", "kg/hr");
        derivative.addOutputVariable("Gas Product.pressure", "bara");
        double[][] temperatureGains = derivative.calculateJacobian();
        if (!Double.isFinite(temperatureGains[0][0]) || !Double.isFinite(temperatureGains[1][0])) {
            throw new IllegalStateException("Temperature sensitivities must be finite");
        }
        DisturbanceVariable temperature = mpc.addDV("Feed", "temperature");
        temperature.setUnit("K");
        temperature.setCvSensitivity(temperatureGains[0][0], temperatureGains[1][0]);

        mpc.setPredictionHorizon(30);
        mpc.setControlHorizon(10);
        mpc.identifyModel(10.0);
        if (!mpc.getLinearizationResult().isSuccessful()) {
            throw new IllegalStateException(mpc.getLinearizationResult().getErrorMessage());
        }

        IndustrialMPCExporter exporter = mpc.createIndustrialExporter();
        exporter.setApplicationName("HP_Separator");
        exporter.setDefaultTimeConstant(60.0);
        exporter.exportStepResponseModel(output.resolve("hp_sep_model.json").toString());
        exporter.exportStepResponseCSV(output.resolve("hp_sep_model.csv").toString());
        exporter.exportComprehensiveConfiguration(output.resolve("hp_sep_config.json").toString());

        SoftSensorExporter softSensor = exporter.createSoftSensorExporter();
        softSensor.addDensitySensor("Gas_Density", "Gas Product", "kg/m3");
        softSensor.addMolecularWeightSensor("Gas_MW", "Gas Product");
        softSensor.exportConfiguration(output.resolve("hp_sep_sensors.json").toString());

        StateVariable gasFlowState = mpc.addSVR("Gas Product", "flowRate", "gas_flow");
        gasFlowState.setUnit("kg/hr");
        gasFlowState.setModelValue(gasProduct.getFlowRate("kg/hr"));
        SubrModlExporter subrModl = mpc.createSubrModlExporter();
        subrModl.setModelName("HP_Sep_NL");
        subrModl.exportConfiguration(output.resolve("hp_sep_subrmodl.cnf").toString());
        logger.info("MPC integration files written to {}", output.toAbsolutePath());
        return mpc;
    }

    public static void main(String[] args) throws Exception {
        configureAndExport(args.length > 0 ? args[0] : "mpc-output");
    }
}

Production Optimization Setup

Use ProductionOptimizer to calculate a steady-state operating target. ProcessLinkedMPC does not expose the objective/weight/priority/export methods formerly shown in this section. Pass the approved target into the configured MPC manipulated-variable workflow separately. The method below requires a solved process with a registered feed named feed; add the plant’s product, power, equipment, and environmental constraints before using its result.

import java.util.Collections;
import neqsim.process.equipment.stream.StreamInterface;
import neqsim.process.processmodel.ProcessSystem;
import neqsim.process.util.optimizer.ProductionOptimizer;
import neqsim.process.util.optimizer.ProductionOptimizer.*;

public class ProductionOptimization {
    public static OptimizationResult calculateTarget(ProcessSystem process) {
        StreamInterface feed = (StreamInterface) process.getUnit("feed");
        OptimizationConfig config = new OptimizationConfig(1000.0, 20000.0)
            .rateUnit("kg/hr")
            .searchMode(SearchMode.BINARY_FEASIBILITY)
            .tolerance(10.0)
            .maxIterations(30);
        OptimizationConstraint installedFeedLimit = OptimizationConstraint.lessThan(
            "Installed feed capacity",
            p -> ((StreamInterface) p.getUnit("feed")).getFlowRate("kg/hr"),
            15000.0,
            ConstraintSeverity.HARD,
            100.0,
            "Maximum installed feed mass rate in kg/hr"
        );
        OptimizationResult result = new ProductionOptimizer().optimize(
            process, feed, config, Collections.emptyList(),
            Collections.singletonList(installedFeedLimit)
        );
        if (!result.isFeasible()) {
            throw new IllegalStateException(result.getInfeasibilityDiagnosis());
        }
        return result;
    }
}

Derivative Calculation for AI and MPC

The Derivative Challenge

AI software and MPC systems typically require derivatives (gradients, Jacobians) of process variables for:

Why Analytical Derivatives Are Difficult

Many NeqSim thermodynamic derivatives are analytical. End-to-end process derivatives can still be difficult to obtain analytically because:

  1. Complex equation chains: Fugacity → Activity Coefficient → Compressibility → Mixing Rules → Pure Component Parameters
  2. Iterative algorithms: Flash calculations use iterative solvers where derivatives require implicit function theorem
  3. Phase transitions: Discontinuities at phase boundaries
  4. Conditional logic: Different correlations for different phases

NeqSim’s Derivative Calculator

NeqSim provides an efficient numerical derivative calculator optimized for process simulations:

import neqsim.process.mpc.ProcessDerivativeCalculator;

// Create calculator
ProcessDerivativeCalculator calc = new ProcessDerivativeCalculator(process);

// Define input variables (what we perturb)
calc.addInputVariable("Feed.flowRate", "kg/hr");
calc.addInputVariable("Feed.pressure", "bara");
calc.addInputVariable("Feed.temperature", "K");

// Define output variables (what we measure)
calc.addOutputVariable("HP Separator.gasOutStream.flowRate", "kg/hr");
calc.addOutputVariable("HP Separator.gasOutStream.pressure", "bara");

// Calculate full Jacobian matrix
double[][] jacobian = calc.calculateJacobian();
// jacobian[i][j] = ∂output_i / ∂input_j

Derivative Methods

Method Formula Accuracy Cost
Forward Difference (f(x+h) - f(x)) / h O(h) N+1 evaluations
Central Difference (f(x+h) - f(x-h)) / 2h O(h²) 2N evaluations
5-Point Stencil Higher-order formula O(h⁴) 4N evaluations
// Select derivative method
calc.setMethod(ProcessDerivativeCalculator.DerivativeMethod.CENTRAL_DIFFERENCE);

// Adjust step size (relative)
calc.setRelativeStepSize(1e-4);  // 0.01% perturbation

Automatic Step Size Selection

The calculator automatically selects appropriate step sizes based on variable type:

Variable Type Minimum Step Rationale
Pressure 0.01 bar Avoid numerical noise
Temperature 0.1 K Sufficient for property changes
Flow Rate 0.001 kg/hr Very small flows need care
Composition 1e-6 Mole fractions are small numbers

Single Derivative

// Get one specific derivative
double dGasFlow_dFeedFlow = calc.getDerivative(
    "HP Separator.gasOutStream.flowRate",  // output
    "Feed.flowRate"                      // input
);

Gradient (One Output, All Inputs)

// Get gradient of one output w.r.t. all inputs
double[] gradient = calc.getGradient("HP Separator.gasOutStream.flowRate");
// gradient[0] = ∂gasFlow/∂feedFlow
// gradient[1] = ∂gasFlow/∂feedPressure
// gradient[2] = ∂gasFlow/∂feedTemperature

Hessian (Second Derivatives)

calculateHessian(outputPath) differentiates the selected registered scalar output with respect to every input pair. The result is a symmetric N×N matrix in input registration order, independently of the number or order of registered outputs. Diagonal entries use a three-point central stencil; mixed entries use four corner evaluations. Both have second-order truncation error for a smooth response. The Hessian uses the configured input step sizes and always runs these central stencils sequentially; setMethod and setParallel control first derivatives.

The standalone example below has three inputs and two outputs. Its selected output is the mass-flow input itself, so every entry of the 3×3 Hessian should be zero within numerical tolerance. This is the regression case from issue #3616.

import org.apache.logging.log4j.LogManager;
import neqsim.process.equipment.stream.Stream;
import neqsim.process.mpc.ProcessDerivativeCalculator;
import neqsim.process.processmodel.ProcessSystem;
import neqsim.thermo.system.SystemSrkEos;

public class ScalarHessianExample {
    public static double[][] calculate() {
        SystemSrkEos fluid = new SystemSrkEos(298.15, 50.0);
        fluid.addComponent("methane", 1.0);
        fluid.setMixingRule("classic");
        Stream feed = new Stream("Feed", fluid);
        feed.setFlowRate(500.0, "kg/hr");
        ProcessSystem process = new ProcessSystem();
        process.add(feed);
        process.run();

        ProcessDerivativeCalculator calc = new ProcessDerivativeCalculator(process);
        calc.addInputVariable("Feed.flowRate", "kg/hr");
        calc.addInputVariable("Feed.pressure", "bara");
        calc.addInputVariable("Feed.temperature", "K");
        calc.addOutputVariable("Feed.flowRate", "kg/hr");
        calc.addOutputVariable("Feed.pressure", "bara");
        return calc.calculateHessian("Feed.flowRate");
    }

    public static void main(String[] args) {
        double[][] hessian = calculate();
        LogManager.getLogger(ScalarHessianExample.class).info(
            "Mass-flow Hessian: {}", java.util.Arrays.deepToString(hessian));
    }
}

The current ProcessDerivativeCalculator.calculateHessian implementation is not suitable for this example: three inputs and two outputs trigger an array bounds error, and the selected-output index is not used in the second-derivative loop. Use the validated Jacobian/gradient workflow above. If an external optimizer needs a Hessian, compute and validate second derivatives of its scalar objective separately; do not assume this helper returns that objective’s Hessian. The implementation defect and reproducer are tracked in issue #3616.

Perturbations preserve the cached base inputs and outputs. On success or an exception, the calculator restores all base inputs and reruns the process. If restoration itself fails, it invalidates the cache and reports that failure, preserving the original calculation exception when present.

The existing calculator accesses variables in their native/default accessor units; the registration unit string does not perform a conversion. This example uses kg/hr, bara and K consistently. A Hessian entry has units of output divided by the two input units. Use independent, writable inputs and a converged process away from phase or control discontinuities. Check sensitivity to step size and solver tolerances: second differences amplify simulation noise.

Export for External Systems

// Export Jacobian to JSON for AI/ML systems
String json = calc.exportJacobianToJSON();

// Export to CSV for spreadsheet analysis
calc.exportJacobianToCSV(output.resolve("jacobian.csv").toString());

JSON Output Format

Illustrative structure for two inputs; numerical values depend on the solved process.

{
  "inputs": ["Feed.flowRate", "Feed.pressure"],
  "outputs": ["HP Separator.gasOutStream.flowRate", "HP Separator.gasOutStream.pressure"],
  "baseInputValues": [100.0, 50.0],
  "baseOutputValues": [85.2, 50.0],
  "jacobian": [
    [0.852, -0.023],
    [0.0, 1.0]
  ]
}

Best Practices for AI Integration

  1. Cache derivatives: Recompute only when operating point changes significantly
  2. Use central differences: More accurate than forward differences
  3. Validate step sizes: Too small causes numerical noise, too large causes truncation error
  4. Monitor for phase changes: Derivatives may jump at phase boundaries
  5. Smooth gradients: For ML training, consider averaging over nearby operating points

Summary

The integration of NeqSim with industrial MPC systems creates a powerful combination for process control and optimization:

Capability NeqSim Role Industrial MPC Role
Model Generation Create physics-based models Execute models in real-time
Constraint Handling Define thermodynamic limits Satisfy constraints online
Production Optimization Quantify capacity limits Push to optimal constraints
Bottleneck Analysis Identify physical causes Calculate economic value
Soft Sensors Provide property calculations Fast lookup/interpolation
Model Validation Rigorous reference Bias detection/correction

This complementary approach combines the accuracy of first-principles thermodynamic modeling with the speed and robustness of industrial control systems.


References