Dynamic Process Simulation Enhancements

This document covers the dynamic simulation improvements added in PR #2064 (dynprocess branch). These features bring NeqSim’s transient simulation capabilities closer to commercial DCS/OTS simulators, covering controller logic, instrumentation realism, equipment-level dynamics, and numerical integration infrastructure.

For the base dynamic simulation setup and DynamicProcessHelper, see Dynamic Simulation with DynamicProcessHelper.

Table of Contents


1. Controller Enhancements

1.1 Controller Modes (AUTO/MANUAL/CASCADE)

Controllers now support the three standard operating modes found in commercial DCS:

Mode Behavior
AUTO PID algorithm computes the output (default)
MANUAL Operator-set output; PID is bypassed but error tracking continues
CASCADE Setpoint received from an upstream (primary) controller

Switching between modes includes bumpless transfer: when transitioning from MANUAL to AUTO, the integral state is back-calculated to match the current manual output so the controller output does not jump.

Package: neqsim.process.controllerdevice

import neqsim.process.controllerdevice.ControllerDeviceInterface.ControllerMode;

// Switch to manual
controller.setMode(ControllerMode.MANUAL);
controller.setManualOutput(45.0); // Set output directly

// Switch back to AUTO with bumpless transfer
controller.setMode(ControllerMode.AUTO);
// Output continues smoothly from 45.0

Key methods on ControllerDeviceInterface:

Method Description
getMode() Returns current ControllerMode
setMode(ControllerMode) Switches mode with bumpless transfer
getManualOutput() Returns the manual output value
setManualOutput(double) Sets the manual output value

1.2 Two-Degree-of-Freedom PID

The PID controller now supports a setpoint weight parameter ($b$) for the proportional term. This decouples the setpoint response from the disturbance response:

\[\text{proportional error} = \text{measurement} - b \cdot \text{setpoint}\]
controller.setSetpointWeight(0.5); // Reduce setpoint kick by 50%
double b = controller.getSetpointWeight();

1.3 Sequential Function Chart (SFC)

A new SequentialFunctionChart class implements IEC 61131-3 style sequence logic for modeling startup/shutdown procedures, ESD logic, and batch operations.

Package: neqsim.process.controllerdevice

An SFC consists of steps (with entry/active/exit actions) connected by transitions (with guard conditions). The chart advances when the active step’s outgoing transition evaluates to true.

SequentialFunctionChart sfc = new SequentialFunctionChart("Startup Sequence");

// Define steps with entry/active/exit actions
SfcStep idle = new SfcStep("IDLE");
SfcStep pressurize = new SfcStep("PRESSURIZE");
pressurize.setEntryAction(() -> valve.setPercentValveOpening(10.0));
SfcStep running = new SfcStep("RUNNING");
running.setEntryAction(() -> valve.setPercentValveOpening(100.0));

sfc.addStep(idle);
sfc.addStep(pressurize);
sfc.addStep(running);

// Transitions with guards
sfc.addTransition("IDLE", "PRESSURIZE", () -> startButton);
sfc.addTransition("PRESSURIZE", "RUNNING",
    () -> separator.getPressure() > 50.0);

// Or timed transitions
sfc.addTimedTransition("RUNNING", "IDLE", 3600.0); // After 1 hour

sfc.start();

// During transient loop
for (int i = 0; i < steps; i++) {
    sfc.runTransient(dt);
    process.runTransient();
}

// Query state
String current = sfc.getActiveStepName(); // "PRESSURIZE"
boolean isRunning = sfc.isRunning();
List<String> history = sfc.getEventHistory();

Key methods on SequentialFunctionChart:

Method Description
addStep(SfcStep) Adds a step (first added becomes initial step)
addTransition(from, to, guard) Adds a conditional transition
addTimedTransition(from, to, seconds) Adds a time-based transition
start() Activates the initial step
stop() Deactivates the chart
reset() Returns to initial step
runTransient(double dt) Advances time and evaluates transitions
getActiveStepName() Returns the currently active step
getEventHistory() Returns the transition event log

1.4 Override (Selector) Control

The OverrideControllerStructure implements HIGH-SELECT or LOW-SELECT logic between two controllers. This is commonly used for safety overrides where a temperature or pressure controller can take over from a flow controller.

Package: neqsim.process.controllerdevice.structure

import neqsim.process.controllerdevice.structure.OverrideControllerStructure;
import neqsim.process.controllerdevice.structure.OverrideControllerStructure.SelectionType;

OverrideControllerStructure override = new OverrideControllerStructure(
    flowController,         // primary (normal operation)
    pressureController,     // override (safety)
    SelectionType.LOW_SELECT  // lowest output wins
);

// In transient loop
override.runTransient(dt);
double output = override.getOutput();
boolean overrideActive = override.isOverrideActive();

1.5 Split-Range Control

The SplitRangeControllerStructure maps a single controller output (0-100%) to multiple final control elements, each assigned a sub-range.

Package: neqsim.process.controllerdevice.structure

import neqsim.process.controllerdevice.structure.SplitRangeControllerStructure;

// Two valves: valve A operates 0-50%, valve B operates 50-100%
SplitRangeControllerStructure splitRange =
    new SplitRangeControllerStructure(controller, 2);

// Or with custom ranges
double[] lows = {0.0, 40.0, 70.0};
double[] highs = {40.0, 70.0, 100.0};
SplitRangeControllerStructure customSplit =
    new SplitRangeControllerStructure(controller, lows, highs);

// In transient loop
splitRange.runTransient(dt);
double valve1 = splitRange.getOutput(0); // 0-100% for element 0
double valve2 = splitRange.getOutput(1); // 0-100% for element 1

2. Instrumentation Realism

2.1 Sensor Fault Injection

Transmitters can now simulate common sensor failure modes for testing control system robustness and operator training scenarios.

Package: neqsim.process.measurementdevice

Fault Type Behavior
NONE Normal operation (default)
STUCK_AT_VALUE Output frozen at the fault parameter value
LINEAR_DRIFT Output drifts at faultParameter units/second
BIAS Constant offset added to the true value
NOISE_BURST Gaussian noise burst (amplitude = fault parameter)
SATURATION Output clamped at the fault parameter value
import neqsim.process.measurementdevice.SensorFaultType;

// Inject a stuck-at fault
pressureTransmitter.setFault(SensorFaultType.STUCK_AT_VALUE, 55.0);

// Inject a drift fault (0.1 bar/second)
pressureTransmitter.setFault(SensorFaultType.LINEAR_DRIFT, 0.1);

// Clear the fault
pressureTransmitter.clearFault();

2.2 Transmitter First-Order Filter

Transmitters can apply a first-order exponential filter (low-pass) to smooth noisy readings. This models the signal damping typically configured on industrial transmitters.

The filter equation per sample:

\[y_k = \alpha \cdot x_k + (1 - \alpha) \cdot y_{k-1}\]

where $\alpha = 1 - e^{-\Delta t / \tau}$ and $\tau$ is the time constant.

// Set a 2-second filter time constant
pressureTransmitter.setFirstOrderTimeConstant(2.0);

// Disable filtering
pressureTransmitter.setFirstOrderTimeConstant(0.0);

// Query
double tau = pressureTransmitter.getFirstOrderTimeConstant();

Typical industrial transmitter time constants range from 0.5 to 10 seconds. A value of 0 (the default) disables the filter entirely.

2.3 Alarm Shelving

Alarms can be temporarily shelved (suppressed) while the alarm state machine continues to track the process value. This models the operator practice of shelving nuisance alarms during maintenance or known upset conditions.

// Shelve indefinitely with a reason
pressureTransmitter.shelveAlarm("Maintenance in progress");

// Shelve until a specific simulation time (e.g., 3600 seconds)
pressureTransmitter.shelveAlarm("Scheduled work", 3600.0);

// Check status
boolean shelved = pressureTransmitter.isAlarmShelved();

// Remove shelve manually
pressureTransmitter.unshelveAlarm();

While shelved:

The underlying AlarmState class provides the shelve(), unshelve(), and isShelved() methods directly if you work with the alarm system outside of transmitters.


3. Valve Nonlinearities

The ThrottlingValve now supports realistic valve dynamics that affect closed-loop control performance:

Parameter Method Description
Deadband setValveDeadband(double) Minimum signal change required before the valve moves (%)
Stiction setValveStiction(double) Static friction — valve sticks until the signal exceeds the breakaway force (%)
Hysteresis setValveHysteresis(double) Difference in valve position between increasing and decreasing signal (%)
ThrottlingValve valve = new ThrottlingValve("CV-101", feed);
valve.setOutletPressure(40.0);

// Configure nonlinearities
valve.setValveDeadband(0.5);   // 0.5% deadband
valve.setValveStiction(2.0);    // 2% stiction
valve.setValveHysteresis(1.0);  // 1% hysteresis

// Query
double db = valve.getValveDeadband();
double st = valve.getValveStiction();
double hy = valve.getValveHysteresis();

These are modeled in the valve’s runTransient() method. The effective valve position may differ from the commanded position due to these nonlinearities, which is critical for control loop performance analysis and valve diagnostics studies.


4. Equipment Dynamics

4.1 Separator Internals

The Separator now models two internal components that affect dynamic behavior:

Weir-Controlled Liquid Outflow

A weir controls the liquid overflow rate using the Francis weir formula:

\[Q_{\text{weir}} = C_d \cdot L_w \cdot (h - h_w)^{3/2}\]

where $L_w$ is the weir length, $h$ is the liquid level, $h_w$ is the weir height, and $C_d$ is the discharge coefficient.

Separator sep = new Separator("HP Sep", feed);
sep.setWeirHeight(0.3);    // 0.3 m weir height
sep.setWeirLength(1.0);    // 1.0 m weir length

// Query the calculated overflow rate (after runTransient)
double qWeir = sep.getWeirOverflowRate(); // m³/s

When both weirHeight and weirLength are set to non-zero values, the weir overflow rate is applied in runTransient() to modulate the liquid outlet flow.

Mist Eliminator Pressure Drop

A mist eliminator (demister pad) adds a velocity-dependent pressure drop to the gas outlet:

\[\Delta P_{\text{mist}} = K \cdot \rho_g \cdot v_g^2 \cdot t\]

where $K$ is the pressure drop coefficient, $\rho_g$ is the gas density, $v_g$ is the gas superficial velocity, and $t$ is the pad thickness.

sep.setMistEliminatorDpCoeff(150.0);      // Coefficient K
sep.setMistEliminatorThickness(0.15);     // 0.15 m pad thickness

// Query the calculated pressure drop (after runTransient)
double dpMist = sep.getMistEliminatorPressureDrop(); // Pa

Boot Volume

For three-phase separators, a boot (sump) volume can be specified:

sep.setBootVolume(0.5); // 0.5 m³ boot volume

4.2 Heat Exchanger Thermal Model

The HeatExchanger now has a full dynamic thermal model with wall energy storage and optional fluid holdup volumes.

Wall Energy ODE

When dynamicModelEnabled is true, the heat exchanger tracks wall temperature using a lumped-parameter energy balance:

\[M_w C_{p,w} \frac{dT_w}{dt} = h_s A (T_{\text{shell}} - T_w) - h_t A (T_w - T_{\text{tube}})\]

where $M_w$ is the wall mass, $C_{p,w}$ is the wall heat capacity, $h_s$ and $h_t$ are the shell-side and tube-side heat transfer coefficients, and $A$ is the heat transfer area.

HeatExchanger hx = new HeatExchanger("E-101", hotStream, coldStream);
hx.setDynamicModelEnabled(true);

// Wall properties
hx.setWallMass(500.0);          // kg
hx.setWallCp(500.0);            // J/(kg·K)
hx.setHeatTransferArea(25.0);   // m²

// Heat transfer coefficients
hx.setShellSideHtc(400.0);     // W/(m²·K)
hx.setTubeSideHtc(800.0);      // W/(m²·K)

Fluid Holdup (CSTR Model)

When holdup volumes are non-zero, the shell and tube fluids are modeled as well-mixed accumulation volumes (CSTR), adding thermal inertia:

\[\rho V C_p \frac{dT_f}{dt} = \dot{m} C_p (T_{\text{in}} - T_f) + h A (T_w - T_f)\]
hx.setShellHoldupVolume(0.5);   // m³ shell-side fluid volume
hx.setTubeHoldupVolume(0.3);    // m³ tube-side fluid volume

With holdup volume = 0 (default), the model reduces to the wall-only ODE.

Key methods:

Method Description
setDynamicModelEnabled(boolean) Enable/disable the dynamic thermal model
setWallMass(double) Wall metal mass in kg
setWallCp(double) Wall heat capacity in J/(kg·K)
setHeatTransferArea(double) Heat transfer area in m²
setShellSideHtc(double) Shell-side HTC in W/(m²·K)
setTubeSideHtc(double) Tube-side HTC in W/(m²·K)
setShellHoldupVolume(double) Shell-side fluid volume in m³
setTubeHoldupVolume(double) Tube-side fluid volume in m³
getWallTemperature() Current wall temperature in K

4.3 Distillation Column MESH Dynamics

The DistillationColumn now supports per-tray dynamic modeling with liquid holdup, energy balance, and vapor hydraulics.

Tray Liquid Holdup

When dynamicColumnEnabled is true, each tray tracks its liquid holdup using the Francis weir overflow formula:

DistillationColumn col = new DistillationColumn("Deethanizer", 10, true, true);
col.setDynamicColumnEnabled(true);
col.setTrayWeirHeight(0.05);  // 5 cm weir height
col.setTrayWeirLength(1.2);   // 1.2 m weir length

// After transient steps, query holdup
double[] holdups = col.getTrayLiquidHoldup(); // m³ per tray

Energy Balance

When dynamicEnergyEnabled is true, per-tray enthalpy is tracked and vapor flow is driven by the tray pressure drop:

col.setDynamicEnergyEnabled(true);
col.setTrayDryPressureDrop(500.0); // 500 Pa dry tray pressure drop

// After transient steps, query per-tray enthalpy
double[] enthalpies = col.getTrayEnthalpy(); // J per tray

The vapor flow through each tray is calculated from:

\[V = \sqrt{\frac{\Delta P_{\text{tray}}}{\rho_V}} \cdot A_{\text{tray}}\]

All dynamic features default to false/0, so existing steady-state column calculations are unaffected.


5. Numerical Infrastructure

5.1 Adaptive Time Stepping

The ProcessSystem now supports adaptive time stepping that automatically adjusts $\Delta t$ based on solution stability:

ProcessSystem process = new ProcessSystem();
// ... add equipment ...
process.run();

process.setAdaptiveTimestepEnabled(true);
process.setMinTimestep(0.001);    // seconds
process.setMaxTimestep(10.0);     // seconds
process.setAdaptiveTimestepTolerance(0.01); // relative tolerance

UUID id = UUID.randomUUID();
double actualDt = process.runTransientAdaptive(1.0, id);
// actualDt may be smaller or larger than the requested 1.0

The adaptive algorithm compares state changes between the full step and two half-steps, reducing or increasing $\Delta t$ based on the relative error.

5.2 Parallel Transient Execution

For large flowsheets, equipment-level transient calculations can be run in parallel threads:

process.setParallelTransientEnabled(true);
process.setTransientThreadPoolSize(4); // Number of worker threads

// Transient steps now run equipment in parallel
process.runTransient();

Note: Parallel execution is beneficial for flowsheets with many independent equipment units. For small flowsheets or tightly coupled equipment (recycles), the overhead may outweigh the benefit.

5.3 Integration Methods

The ProcessSystem supports selectable integration methods:

import neqsim.process.processmodel.ProcessSystem.IntegrationMethod;

process.setIntegrationMethod(IntegrationMethod.EXPLICIT_EULER);   // Default
process.setIntegrationMethod(IntegrationMethod.RUNGE_KUTTA_4);    // Higher-order
Method Order Stability Cost
EXPLICIT_EULER 1st Conditional 1 evaluation/step
RUNGE_KUTTA_4 4th Better 4 evaluations/step

6. Test Coverage

All features are covered by three test classes with 59 total tests:

Test Class Tests Coverage
DynamicImprovementsTest 17 Controller modes, 2-DOF PID, SFC, control structures, gain scheduling, event logging, performance metrics
DynamicImprovementsPhase2Test 26 Sensor faults, valve nonlinearities, adaptive timestep, parallel transient, integration methods, JSON process builder
DynamicImprovementsPhase3Test 16 Transmitter filter, alarm shelving, separator internals, HX thermal model, distillation MESH dynamics