Dynamic Process Simulation Enhancements

This document covers the dynamic simulation improvements added in PR #2064 (dynprocess branch). These features bring NeqSim’s transient simulation capabilities closer to commercial DCS/OTS simulators, covering controller logic, instrumentation realism, equipment-level dynamics, and numerical integration infrastructure.

For the base dynamic simulation setup and DynamicProcessHelper, see Dynamic Simulation with DynamicProcessHelper.

Table of Contents


1. Controller Enhancements

1.1 Controller Modes (AUTO/MANUAL/CASCADE)

Controllers now support the three standard operating modes found in commercial DCS:

Mode Behavior
AUTO PID algorithm computes the output (default)
MANUAL Operator-set output; PID is bypassed but error tracking continues
CASCADE Setpoint received from an upstream (primary) controller

Switching between modes includes bumpless transfer: when transitioning from MANUAL to AUTO, the integral state is back-calculated to match the current manual output so the controller output does not jump.

Package: neqsim.process.controllerdevice

import neqsim.process.controllerdevice.ControllerDeviceInterface.ControllerMode;

// Switch to manual
controller.setMode(ControllerMode.MANUAL);
controller.setManualOutput(45.0); // Set output directly

// Switch back to AUTO with bumpless transfer
controller.setMode(ControllerMode.AUTO);
// Output continues smoothly from 45.0

Key methods on ControllerDeviceInterface:

Method Description
getMode() Returns current ControllerMode
setMode(ControllerMode) Switches mode with bumpless transfer
getManualOutput() Returns the manual output value
setManualOutput(double) Sets the manual output value

1.2 Two-Degree-of-Freedom PID

The PID controller now supports a setpoint weight parameter ($b$) for the proportional term. This decouples the setpoint response from the disturbance response:

\[\text{proportional error} = \text{measurement} - b \cdot \text{setpoint}\]
controller.setSetpointWeight(0.5); // Reduce setpoint kick by 50%
double b = controller.getSetpointWeight();

1.3 Sequential Function Chart (SFC)

A new SequentialFunctionChart class implements IEC 61131-3 style sequence logic for modeling startup/shutdown procedures, ESD logic, and batch operations.

Package: neqsim.process.controllerdevice

An SFC consists of steps (with entry/active/exit actions) connected by transitions (with guard conditions). The chart advances when the active step’s outgoing transition evaluates to true.

SequentialFunctionChart sfc = new SequentialFunctionChart("Startup Sequence");

// Define steps with entry/active/exit actions
SfcStep idle = new SfcStep("IDLE");
SfcStep pressurize = new SfcStep("PRESSURIZE");
pressurize.setEntryAction(() -> valve.setPercentValveOpening(10.0));
SfcStep running = new SfcStep("RUNNING");
running.setEntryAction(() -> valve.setPercentValveOpening(100.0));

sfc.addStep(idle);
sfc.addStep(pressurize);
sfc.addStep(running);

// Transitions with guards
sfc.addTransition("IDLE", "PRESSURIZE", () -> startButton);
sfc.addTransition("PRESSURIZE", "RUNNING",
    () -> separator.getPressure() > 50.0);

// Or timed transitions
sfc.addTimedTransition("RUNNING", "IDLE", 3600.0); // After 1 hour

sfc.start();

// During transient loop
for (int i = 0; i < steps; i++) {
    sfc.runTransient(dt);
    process.runTransient();
}

// Query state
String current = sfc.getActiveStepName(); // "PRESSURIZE"
boolean isRunning = sfc.isRunning();
List<String> history = sfc.getEventHistory();

Key methods on SequentialFunctionChart:

Method Description
addStep(SfcStep) Adds a step (first added becomes initial step)
addTransition(from, to, guard) Adds a conditional transition
addTimedTransition(from, to, seconds) Adds a time-based transition
start() Activates the initial step
stop() Deactivates the chart
reset() Returns to initial step
runTransient(double dt) Advances time and evaluates transitions
getActiveStepName() Returns the currently active step
getEventHistory() Returns the transition event log

1.4 Override (Selector) Control

The OverrideControllerStructure implements HIGH-SELECT or LOW-SELECT logic between two controllers. This is commonly used for safety overrides where a temperature or pressure controller can take over from a flow controller.

Package: neqsim.process.controllerdevice.structure

import neqsim.process.controllerdevice.structure.OverrideControllerStructure;
import neqsim.process.controllerdevice.structure.OverrideControllerStructure.SelectionType;

OverrideControllerStructure override = new OverrideControllerStructure(
    flowController,         // primary (normal operation)
    pressureController,     // override (safety)
    SelectionType.LOW_SELECT  // lowest output wins
);

// In transient loop
override.runTransient(dt);
double output = override.getOutput();
boolean overrideActive = override.isOverrideActive();

1.5 Split-Range Control

The SplitRangeControllerStructure maps a single controller output (0-100%) to multiple final control elements, each assigned a sub-range.

Package: neqsim.process.controllerdevice.structure

import neqsim.process.controllerdevice.structure.SplitRangeControllerStructure;

// Two valves: valve A operates 0-50%, valve B operates 50-100%
SplitRangeControllerStructure splitRange =
    new SplitRangeControllerStructure(controller, 2);

// Or with custom ranges
double[] lows = {0.0, 40.0, 70.0};
double[] highs = {40.0, 70.0, 100.0};
SplitRangeControllerStructure customSplit =
    new SplitRangeControllerStructure(controller, lows, highs);

// In transient loop
splitRange.runTransient(dt);
double valve1 = splitRange.getOutput(0); // 0-100% for element 0
double valve2 = splitRange.getOutput(1); // 0-100% for element 1

2. Instrumentation Realism

2.1 Sensor Fault Injection

Transmitters can now simulate common sensor failure modes for testing control system robustness and operator training scenarios.

Package: neqsim.process.measurementdevice

Fault Type Behavior
NONE Normal operation (default)
STUCK_AT_VALUE Output frozen at the fault parameter value
LINEAR_DRIFT Output drifts at faultParameter units/second
BIAS Constant offset added to the true value
NOISE_BURST Gaussian noise burst (amplitude = fault parameter)
SATURATION Output clamped at the fault parameter value
import neqsim.process.measurementdevice.SensorFaultType;

// Inject a stuck-at fault
pressureTransmitter.setFault(SensorFaultType.STUCK_AT_VALUE, 55.0);

// Inject a drift fault (0.1 bar/second)
pressureTransmitter.setFault(SensorFaultType.LINEAR_DRIFT, 0.1);

// Clear the fault
pressureTransmitter.clearFault();

2.2 Transmitter First-Order Filter

Transmitters can apply a first-order exponential filter (low-pass) to smooth noisy readings. This models the signal damping typically configured on industrial transmitters.

The filter equation per sample:

\[y_k = \alpha \cdot x_k + (1 - \alpha) \cdot y_{k-1}\]

where $\alpha = 1 - e^{-\Delta t / \tau}$ and $\tau$ is the time constant.

// Set a 2-second filter time constant
pressureTransmitter.setFirstOrderTimeConstant(2.0);

// Disable filtering
pressureTransmitter.setFirstOrderTimeConstant(0.0);

// Query
double tau = pressureTransmitter.getFirstOrderTimeConstant();

Typical industrial transmitter time constants range from 0.5 to 10 seconds. A value of 0 (the default) disables the filter entirely.

2.3 Alarm Shelving

Alarms can be temporarily shelved (suppressed) while the alarm state machine continues to track the process value. This models the operator practice of shelving nuisance alarms during maintenance or known upset conditions.

// Shelve indefinitely with a reason
pressureTransmitter.shelveAlarm("Maintenance in progress");

// Shelve until a specific simulation time (e.g., 3600 seconds)
pressureTransmitter.shelveAlarm("Scheduled work", 3600.0);

// Check status
boolean shelved = pressureTransmitter.isAlarmShelved();

// Remove shelve manually
pressureTransmitter.unshelveAlarm();

While shelved:

The underlying AlarmState class provides the shelve(), unshelve(), and isShelved() methods directly if you work with the alarm system outside of transmitters.


3. Valve Nonlinearities

The ThrottlingValve now supports realistic valve dynamics that affect closed-loop control performance:

Parameter Method Description
Deadband setValveDeadband(double) Minimum signal change required before the valve moves (%)
Stiction setValveStiction(double) Static friction — valve sticks until the signal exceeds the breakaway force (%)
Hysteresis setValveHysteresis(double) Difference in valve position between increasing and decreasing signal (%)
ThrottlingValve valve = new ThrottlingValve("CV-101", feed);
valve.setOutletPressure(40.0);

// Configure nonlinearities
valve.setValveDeadband(0.5);   // 0.5% deadband
valve.setValveStiction(2.0);    // 2% stiction
valve.setValveHysteresis(1.0);  // 1% hysteresis

// Query
double db = valve.getValveDeadband();
double st = valve.getValveStiction();
double hy = valve.getValveHysteresis();

These are modeled in the valve’s runTransient() method. The effective valve position may differ from the commanded position due to these nonlinearities, which is critical for control loop performance analysis and valve diagnostics studies.


4. Equipment Dynamics

4.1 Separator Internals

The Separator now models two internal components that affect dynamic behavior:

Weir-Controlled Liquid Outflow

A weir controls the liquid overflow rate using the Francis weir formula:

\[Q_{\text{weir}} = C_d \cdot L_w \cdot (h - h_w)^{3/2}\]

where $L_w$ is the weir length, $h$ is the liquid level, $h_w$ is the weir height, and $C_d$ is the discharge coefficient.

Separator sep = new Separator("HP Sep", feed);
sep.setWeirHeight(0.3);    // 0.3 m weir height
sep.setWeirLength(1.0);    // 1.0 m weir length

// Query the calculated overflow rate (after runTransient)
double qWeir = sep.getWeirOverflowRate(); // m³/s

When both weirHeight and weirLength are set to non-zero values, the weir overflow rate is applied in runTransient() to modulate the liquid outlet flow.

Mist Eliminator Pressure Drop

A mist eliminator (demister pad) adds a velocity-dependent pressure drop to the gas outlet:

\[\Delta P_{\text{mist}} = K \cdot \rho_g \cdot v_g^2 \cdot t\]

where $K$ is the pressure drop coefficient, $\rho_g$ is the gas density, $v_g$ is the gas superficial velocity, and $t$ is the pad thickness.

sep.setMistEliminatorDpCoeff(150.0);      // Coefficient K
sep.setMistEliminatorThickness(0.15);     // 0.15 m pad thickness

// Query the calculated pressure drop (after runTransient)
double dpMist = sep.getMistEliminatorPressureDrop(); // Pa

Boot Volume

For three-phase separators, a boot (sump) volume can be specified:

sep.setBootVolume(0.5); // 0.5 m³ boot volume

4.2 Heat Exchanger Thermal Model

The HeatExchanger now has a full dynamic thermal model with wall energy storage and optional fluid holdup volumes.

Wall Energy ODE

When dynamicModelEnabled is true, the heat exchanger tracks wall temperature using a lumped-parameter energy balance:

\[M_w C_{p,w} \frac{dT_w}{dt} = h_s A (T_{\text{shell}} - T_w) - h_t A (T_w - T_{\text{tube}})\]

where $M_w$ is the wall mass, $C_{p,w}$ is the wall heat capacity, $h_s$ and $h_t$ are the shell-side and tube-side heat transfer coefficients, and $A$ is the heat transfer area.

HeatExchanger hx = new HeatExchanger("E-101", hotStream, coldStream);
hx.setDynamicModelEnabled(true);

// Wall properties
hx.setWallMass(500.0);          // kg
hx.setWallCp(500.0);            // J/(kg·K)
hx.setHeatTransferArea(25.0);   // m²

// Heat transfer coefficients
hx.setShellSideHtc(400.0);     // W/(m²·K)
hx.setTubeSideHtc(800.0);      // W/(m²·K)

Fluid Holdup (CSTR Model)

When holdup volumes are non-zero, the shell and tube fluids are modeled as well-mixed accumulation volumes (CSTR), adding thermal inertia:

\[\rho V C_p \frac{dT_f}{dt} = \dot{m} C_p (T_{\text{in}} - T_f) + h A (T_w - T_f)\]
hx.setShellHoldupVolume(0.5);   // m³ shell-side fluid volume
hx.setTubeHoldupVolume(0.3);    // m³ tube-side fluid volume

With holdup volume = 0 (default), the model reduces to the wall-only ODE.

Key methods:

Method Description
setDynamicModelEnabled(boolean) Enable/disable the dynamic thermal model
setWallMass(double) Wall metal mass in kg
setWallCp(double) Wall heat capacity in J/(kg·K)
setHeatTransferArea(double) Heat transfer area in m²
setShellSideHtc(double) Shell-side HTC in W/(m²·K)
setTubeSideHtc(double) Tube-side HTC in W/(m²·K)
setShellHoldupVolume(double) Shell-side fluid volume in m³
setTubeHoldupVolume(double) Tube-side fluid volume in m³
getWallTemperature() Current wall temperature in K

4.3 Distillation Column MESH Dynamics

The DistillationColumn now supports per-tray dynamic modeling with liquid holdup, energy balance, and vapor hydraulics.

Tray Liquid Holdup

When dynamicColumnEnabled is true, each tray tracks its liquid holdup using the Francis weir overflow formula:

DistillationColumn col = new DistillationColumn("Deethanizer", 10, true, true);
col.setDynamicColumnEnabled(true);
col.setTrayWeirHeight(0.05);  // 5 cm weir height
col.setTrayWeirLength(1.2);   // 1.2 m weir length

// After transient steps, query holdup
double[] holdups = col.getTrayLiquidHoldup(); // m³ per tray

Energy Balance

When dynamicEnergyEnabled is true, per-tray enthalpy is tracked and vapor flow is driven by the tray pressure drop:

col.setDynamicEnergyEnabled(true);
col.setTrayDryPressureDrop(500.0); // 500 Pa dry tray pressure drop

// After transient steps, query per-tray enthalpy
double[] enthalpies = col.getTrayEnthalpy(); // J per tray

The vapor flow through each tray is calculated from:

\[V = \sqrt{\frac{\Delta P_{\text{tray}}}{\rho_V}} \cdot A_{\text{tray}}\]

All dynamic features default to false/0, so existing steady-state column calculations are unaffected.


5. Numerical Infrastructure

5.1 Adaptive Time Stepping

The ProcessSystem now supports adaptive time stepping that automatically adjusts $\Delta t$ based on solution stability:

ProcessSystem process = new ProcessSystem();
// ... add equipment ...
process.run();

process.setAdaptiveTimestepEnabled(true);
process.setMinTimestep(0.001);    // seconds
process.setMaxTimestep(10.0);     // seconds
process.setAdaptiveTimestepTolerance(0.01); // relative tolerance

UUID id = UUID.randomUUID();
double actualDt = process.runTransientAdaptive(1.0, id);
// actualDt may be smaller or larger than the requested 1.0

Every ProcessSystem and ProcessModel transient entry point requires a finite, positive timestep. Zero, negative, NaN, and infinite values throw IllegalArgumentException before snapshots, setters, events, process areas, equipment, controllers, clocks, or identifiers can change. Adaptive stepping rejects invalid requested values instead of silently clamping them.

A multi-area ProcessModel also requires every child ProcessSystem to start the step on the same finite simulation clock. A material mismatch throws IllegalStateException before the first area advances or a shared EventScheduler fires. Reset or explicitly synchronize restored, copied, or independently advanced areas before calling ProcessModel.runTransient(...); this prevents one scheduled event from affecting only the areas that happen to run later in the insertion order.

The adaptive algorithm compares state changes between the full step and two half-steps, reducing or increasing $\Delta t$ based on the relative error.

Setter units form a dedicated pre-step specification phase. Each setter receives exactly one runTransient(dt, id) call per process timestep, so its specification is applied once and its own clock advances by the same $\Delta t$ as the process. Setters are excluded from the later explicit, semi-implicit, and parallel equipment passes.

Controller execution is coalesced by object identity and timestep calculation identifier. Equipment that actually integrates a controller passes the same calculation identifier to the controller; registering that object separately with process.add(controller) therefore keeps it discoverable without advancing its time, integral, derivative, or event-log state twice. Merely attaching a controller to equipment that does not execute it does not suppress the standalone update. Repeated standalone registration is also coalesced to one update per timestep; distinct controller objects remain independent even if they share a name. ControllerDeviceBaseClass tracks the identifier automatically and makes repeated calls with one identifier idempotent, including semi-implicit equipment passes. Custom controller implementations that integrate inside equipment should implement hasRunTransient(UUID) and the same one-update-per-identifier contract.

Steady-state equipment can be evaluated more than once while a solver refines one physical timestep. The default SimulationInterface.runTransient(dt, id) still executes run(id) on every evaluation, so algebraic recycles retain both semi-implicit passes, but advances the equipment clock only on the first successful evaluation of a non-null calculation identifier. A new identifier advances time for the next physical step. This keeps algebraic solver iterations separate from simulated time, including normal low-flow returns.

5.2 Parallel Transient Execution

For large flowsheets, equipment-level transient calculations can be run in parallel threads:

process.setParallelTransientEnabled(true);
process.setTransientThreadPoolSize(4); // Number of worker threads

// Transient steps now run equipment in parallel
process.runTransient();

The configured workers are reused across timesteps. NeqSim creates the executor lazily for each ProcessSystem, keeps it out of serialized model state, and allows idle daemon workers to time out after 60 seconds. Changing setTransientThreadPoolSize(...) or disabling parallel transient execution retires the existing pool. This avoids creating and destroying a complete thread pool for every timestep in long dynamic studies.

Parallel transient execution uses the same cached process graph as steady-state parallel execution. Equipment is partitioned into topological levels: all upstream groups in one level finish before downstream equipment is submitted, while independent groups in the same level can use separate workers. Groups that must share mutable inlet state execute sequentially within one worker. This prevents a downstream unit from observing a partially updated upstream stream merely because both units were submitted in the same timestep.

If the thread calling runTransient(...) is interrupted while waiting for parallel equipment, NeqSim restores the caller’s interrupt status and stops waiting. No downstream level is submitted. Later parallel passes in the same timestep observe that status and do not submit additional equipment work. Queued futures are cancelled without interrupting equipment already updating state. Because those running updates are not transactionally interruptible, NeqSim aborts the remaining controller, measurement, result-storage, and event-publication phases for that timestep. Callers should still treat an interrupted timestep as incomplete rather than as an atomic rollback.

Note: Parallel execution is beneficial for flowsheets with many independent branches. Topological ordering covers feed-forward stream dependencies, but it does not define iteration or rollback for recycle loops and other implicit couplings. Keep the option disabled for those cases until their transient convergence contract is explicitly supported. For small flowsheets, the scheduling overhead may also outweigh the benefit.

5.3 Integration Methods

The ProcessSystem supports selectable integration methods:

import neqsim.process.processmodel.ProcessSystem.IntegrationMethod;

process.setIntegrationMethod(IntegrationMethod.EXPLICIT_EULER);   // Default
process.setIntegrationMethod(IntegrationMethod.RUNGE_KUTTA_4);    // Higher-order
Method Order Stability Cost
EXPLICIT_EULER 1st Conditional 1 evaluation/step
RUNGE_KUTTA_4 4th Better 4 evaluations/step

6. Test Coverage

The features in this guide are covered by eight focused test classes with 85 total tests:

Test Class Tests Coverage
DynamicImprovementsTest 17 Controller modes, 2-DOF PID, SFC, control structures, gain scheduling, event logging, performance metrics
DynamicImprovementsPhase2Test 27 Sensor faults, valve nonlinearities, adaptive timestep, parallel transient, integration methods, JSON process builder
DynamicImprovementsPhase3Test 16 Transmitter filter, alarm shelving, separator internals, HX thermal model, distillation MESH dynamics
ProcessSystemParallelTransientTest 9 Worker reuse, copy lifecycle, dependency ordering, independent-level concurrency, and interruption behavior at waits and level boundaries
ProcessSystemTransientSetterTest 3 Single setter application, repeated-step clock advancement, and explicit, semi-implicit, and parallel execution
ProcessSystemTransientControllerTest 5 Equipment execution, semi-implicit passes, attachment-only fallback, duplicate standalone registration, identity semantics, and repeated timesteps
ProcessSystemTransientAlgebraicTimeTest 4 Repeated algebraic evaluation, semi-implicit recycle iteration, low-flow completion identifiers, null-ID compatibility, and one clock advance per timestep
ProcessSystemTransientTimestepValidationTest 4 Finite-positive process, adaptive, and multi-area timestep preflight plus valid nearby steps

Run all tests:

./mvnw test -Dtest=DynamicImprovementsTest,DynamicImprovementsPhase2Test,DynamicImprovementsPhase3Test,ProcessSystemParallelTransientTest,ProcessSystemTransientSetterTest,ProcessSystemTransientControllerTest,ProcessSystemTransientAlgebraicTimeTest,ProcessSystemTransientTimestepValidationTest