Heat exchanger automation with native P&ID and DEXPI

HeatExchangerAutomationWorkflow connects the existing native instrumentation, controller, canonical P&ID, DEXPI 2.0.1 and drawing exporters. The same live TT, PID and utility valve objects drive the simulation and the engineering package. The native four-port exchanger drawing keeps the process and utility circuits separate, including actual upstream valves and stream-mounted measurements.

The complete executable natural-gas/reference-water example is HeatExchangerAutomationWorkflowTest. Its tests build, instrument, export, reload, tune and revise the public example; the test data are illustrative study inputs.

Automatic workflow

  1. Build the two feeds and an actual ThrottlingValve on the utility inlet. Give every material stream and equipment item a unique tag. Put the feeds, valve and exchanger in that execution order in a ProcessSystem.
  2. Use HeatExchanger for the two-circuit thermal model. Supply wall mass and heat capacity, nominal fluid volumes, area and both film coefficients. Enable setDynamicModelEnabled(true) before instrumentation and the initial run. Use reference water or seawater for the utility as described in reference cooling water.
  3. Call HeatExchangerAutomationWorkflow.instrument with the actual exchanger tag, utility valve tag, project identity and Settings. It initializes the thermal state and creates nine actual devices: TT and PT at all four ports, plus an FT at the utility inlet. A native outlet-temperature TIC manipulates the existing utility valve. Settings allocate two adjacent numbers per circuit.
  4. Build the current canonical graph with PidNativeControlSystem.fromProcess and explicit bindings with PidNativeControlSystem.bind.
  5. Call HeatExchangerControllerTuning.tune with a Definition containing the controller tag, temperature target, timestep, duration, final hold window, temperature tolerance, maximum thermal residual and an array of Kp/Ti/Td candidates. Each candidate runs the actual native loop on an independent process copy. Read the candidate failures, traces, saturation and response metrics.
  6. Apply an accepted recommendation through applyRecommendation with an explicit new revision. Reimport the graph and bindings after revision.
  7. Call HeatExchangerAutomationWorkflow.export with explicit DEXPI provenance, a new output directory and the optional executed tuning result.

The initial automated loop uses Celsius, engineering-unit PID gains and a 5–100% valve range. It assumes increasing cooling-water flow reduces the controlled outlet temperature. Verify this physical sign and valve authority for the actual case. A heating service, cascade loop, split range, bypass or another actuator needs its own explicit design rather than this cooling-loop helper.

Thermal model and units

With thermal dynamics enabled, the existing HeatExchanger uses the same three-node model for both run and runTransient: two completely mixed, single-phase fluid inventories exchanging heat with a metal wall. For each fluid $i$,

\[M_i\frac{h_i^{n+1}-h_i^n}{\Delta t} =\dot m_i(h_{i,\mathrm{in}}-h_i^{n+1}) -K_i(T_i^{n+1}-T_w^{n+1}),\]

and for the wall,

\[M_w C_w\frac{T_w^{n+1}-T_w^n}{\Delta t} =\sum_i K_i(T_i^{n+1}-T_w^{n+1}),\qquad K_i=\alpha_i A.\]

The nonlinear backward-Euler solve evaluates actual NeqSim enthalpy and Cp, using a bounded Newton iteration and EJML. The reported thermal ledger includes both fluid enthalpy inventories and the wall. It is a constant-pressure thermal model, with mass flow in kg/s, enthalpy in J/kg, wall Cp in J/(kg K), area in m², film coefficients in W/(m² K), nominal volumes in m³ and time in seconds.

run initializes each fixed fluid mass from its solved density and nominal volume. The volumes are initialization inputs; constant geometric volume, thermal expansion and pressure evolution are not solved. Zero nominal fluid volume gives an algebraic fluid node. Both inlet flows must stay positive. Pressure, composition, salinity and supported thermodynamic model parameters remain fixed during transient execution. Reinitialize deliberately with run after changing the inventory basis. The audited fluid classes are SystemSrkEos, SystemPrEos, SystemWaterIF97 and SystemSeawater, with classical cubic-EOS mixing for the EOS fluids. Other classes and mixing rules fail closed. Composition comparison ignores normalization roundoff below 1e-12 mole fraction.

The configured steady NTU/UA specification is retained but inactive in thermal mode. The lumped model excludes distributed counterflow, pressure drop, phase change and hydraulic hammer. Disable thermal dynamics to use the default steady specification.

Evidence, repeatability and restart

getLastThermalBalance exposes interval accumulation, boundary energy and residual in joules. Reusing a physical UUID recomputes from that interval’s retained start state and advances the clock once; use a new UUID for each next interval. Changing the duration for an existing UUID is rejected. Native snapshots restore the existing outlet objects and retained physical interval.

For dynamic continuation, save the process with saveToNeqsim and reload with NeqSimXtream.openNeqsim, casting the returned object to ProcessSystem. ProcessSystem.loadFromNeqsim intentionally calls run and reinitializes steady state, so it is not a dynamic-restart operation.

Tuning freezes the complete serialized source process after normalizing only the selected controller’s gains and setpoint on an isolated copy. This includes thermodynamic parameters, controller history, sensor sample holds, valve state and all process clocks. Changed source state or non-tunable policy invalidates the evidence. The hash is a same-build state guard, not a durable cross-version interchange identifier. Candidates share one frozen initial state and differ only in the declared gains and target.

Acceptance requires the declared final hold window and thermal residual limit. The lowest integral absolute error among passing candidates is recommended. No passing candidate gives NO_ACCEPTABLE_CANDIDATE. A recommendation covers the declared case and timestep; establish refinement and disturbance/saturation performance for a plant-specific tuning study.

Coordinated package

The exporter prepares a private package and moves it to a new directory, using an atomic move where supported. It includes native PFD/P&ID PDFs, SVG and layout companions, DEXPI XML, canonical P&ID, explicit object bindings, automation registers, saved native simulation model, thermal configuration, manifest and optional tuning trace/readback. The tuning receipt states whether the exported actual gains match the tested candidate.

DEXPI carries typed plant and signal identities. The full executable control policy and transient settings remain in the coordinated canonical sidecar and native model; XML alone is not PLC parameter transfer. Import/export and simulation validation do not establish receiving-tool or hardware qualification.

Missing line design, relief sizing, valve fail action and safety functions remain explicit HOLD items. Automatic basic instrumentation does not infer those design requirements or construction approval. See the existing heat exchanger models for other thermal formulations.

One exchanger in both execution modes

Use the existing HeatExchanger with setDynamicModelEnabled(true); the default remains the existing steady specification, including NTU/UA, rating, approach-temperature and specified-outlet paths. Enabling thermal dynamics selects the two mixed fluid inventories and metal wall on the same object. run() then establishes that model’s steady equilibrium, and runTransient(dt, id) advances its coupled backward-Euler enthalpy balances. Film coefficients and area govern this thermal model. The configured steady UA is retained for returning to the default mode and is reported separately as steadyOnlyUaWPerK in its thermal configuration.

Changing mode clears thermal inventory, repeated-interval history and steady caches. It preserves stream objects, instrumentation references, the internal calculated heatDuty port and all tags. The first transient interval initializes inventory from the currently published outlet temperatures on the live inlet pressure/composition basis. To start instead from the thermal model’s equilibrium, call run() after enabling. Disabling returns to the established steady calculation; a subsequent enable starts a new inventory. Thermal mode requires positive wall capacity, film coefficients and area, nonnegative nominal fluid volumes, positive flows, and fixed pressure/composition single-phase fluids. External or specified heat boundaries are rejected before changing the mode.

Snapshots cover the concrete enabled exchanger, both outlets, inherited heater specifications, utility specification and internal port result. Unsupported subclasses, mutable rating calculators, runtime capacity constraints and external energy connections fail closed. A deep copy() creates an independent participant identity; saved process state retains its identity for continuation. Legacy Java-serialized exchangers acquire a unique identity when first accessed.

Dynamic monitoring reports thermalModel, configuredSteadyUAvalue and the accepted thermalBalance receipt. Steady-only effectiveness, duty ratio and active UA are omitted while thermal mode is enabled. This avoids stale NTU values and keeps the JSON valid. Nonlinear solves target a maximum equation residual of 1e-5 W, relaxed at sub-second steps only to retain a 1e-5 J per-equation energy budget when temperature updates reach floating-point resolution.

Initialize the selected mode before observing the ML state vector or capturing its feature names. Thermal mode reports wall_temperature in K instead of the steady UA/effectiveness features; its feature order stays stable across subsequent timesteps. A mode change requires run() (or the first thermal runTransient) before observation, so arrays never expose stale undefined effectiveness.

Steady observation vectors omit an undefined effectiveness for specified-outlet or approach-temperature calculations.