Motor Mechanical Design

NeqSim provides a MotorMechanicalDesign class for the physical and mechanical aspects of electric motor specification, complementing the electrical design handled by ElectricalDesign and ElectricalMotor. Together with EquipmentDesignReport, this enables a complete motor and equipment design from a single process simulation result.

When to Use

You need … Use class
Motor electrical sizing (kW, voltage, efficiency class) ElectricalDesign / ElectricalMotor
Motor physical design (foundation, vibration, cooling, bearings, noise) MotorMechanicalDesign
Combined mechanical + electrical + motor report EquipmentDesignReport

Standards Reference

Standard Scope Used In
IEC 60034-1 Rating and performance, derating Altitude and temperature derating
IEC 60034-5 Degrees of protection (IP code) Enclosure / IP rating
IEC 60034-6 Methods of cooling (IC code) Cooling classification
IEC 60034-9 Noise limits Sound power level limits
IEC 60034-14 Mechanical vibration Vibration grade A/B limits
IEC 60034-30-1 Efficiency classes (IE1–IE4) Motor sizing (via ElectricalMotor)
IEEE 841 Petroleum/chemical industry motors Foundation ratio (3:1), min bearing life
ISO 10816-3 Vibration evaluation — industrial machines Vibration zone classification (A/B/C/D)
ISO 281 Rolling bearing life calculation L10 bearing life
NORSOK E-001 Electrical systems (offshore) Motor installation requirements
NORSOK S-002 Working environment Noise limit 83 dB(A) at 1 m
IEC 60079 Equipment for explosive atmospheres Ex marking for Zone 0/1/2

Quick Start

// Standalone — from known shaft power
MotorMechanicalDesign motorDesign = new MotorMechanicalDesign(250.0); // 250 kW
motorDesign.setPoles(4);
motorDesign.setAmbientTemperatureC(45.0);
motorDesign.setAltitudeM(500.0);
motorDesign.setHazardousZone(1);
motorDesign.setGasGroup("IIA");
motorDesign.calcDesign();

System.out.println(motorDesign.toJson());
// From electrical design — reads motor parameters automatically
Compressor comp = new Compressor("export", feed);
comp.setOutletPressure(80.0);
comp.run();

ElectricalDesign elecDesign = comp.getElectricalDesign();
elecDesign.calcDesign();

MotorMechanicalDesign motorDesign = new MotorMechanicalDesign(elecDesign);
motorDesign.calcDesign();

System.out.println("Foundation mass: " + motorDesign.getRequiredFoundationMassKg() + " kg");
System.out.println("Vibration zone:  " + motorDesign.getVibrationZone());
System.out.println("Cooling code:    " + motorDesign.getCoolingCode());
System.out.println("L10 bearing life:" + motorDesign.getBearingL10LifeHours() + " hours");
System.out.println("Noise at 1m:     " + motorDesign.getSoundPressureLevelAt1mDbA() + " dB(A)");
System.out.println("NORSOK S-002 OK: " + motorDesign.isNoiseWithinNorsokLimit());

Design Calculations

1. Environmental Derating (IEC 60034-1)

Motors are rated at standard conditions: 40 °C ambient, altitude up to 1000 m. Beyond these limits, output must be derated:

Altitude derating:

\[f_{\text{alt}} = 1 - \frac{\max(0,\; h - 1000)}{100} \times 0.01\]

where $h$ is altitude in meters. Each 100 m above 1000 m reduces output by 1%.

Temperature derating:

\[f_{\text{temp}} = 1 - \max(0,\; T_{\text{amb}} - 40) \times 0.025\]

where $T_{\text{amb}}$ is ambient temperature in °C. Each degree above 40 °C reduces output by 2.5%.

Combined derating:

\[f_{\text{combined}} = f_{\text{alt}} \times f_{\text{temp}}\]

2. Foundation Design (IEEE 841)

Static load — motor weight:

\[F_{\text{static}} = m_{\text{motor}} \times g\]

Dynamic load — due to residual unbalance per IEC 60034-14 Grade A:

\[F_{\text{dynamic}} \approx 0.1 \times F_{\text{static}}\]

Foundation mass — IEEE 841 recommends a minimum 3:1 mass ratio (concrete foundation to motor weight) for adequate vibration isolation:

\[m_{\text{foundation}} = 3 \times m_{\text{motor}}\]

Foundation type recommendation:

Motor Power Foundation Type
< 75 kW Steel baseplate on concrete pad
75 – 500 kW Concrete block foundation
> 500 kW Concrete block with spring isolation

3. Cooling Classification (IEC 60034-6)

IC Code Description Power Range
IC411 TEFC — totally enclosed, fan-cooled ≤ 315 kW
IC611 Separate external fan (forced ventilation) 315 – 2000 kW
IC81W Water-cooled (closed circuit) > 2000 kW

Heat dissipation is estimated from motor efficiency:

\[Q_{\text{loss}} = P_{\text{shaft}} \times \left(\frac{1}{\eta} - 1\right)\]

4. Bearing Selection (ISO 281)

Motor Power Bearing Type
< 200 kW Deep groove ball bearings
200 – 1000 kW Cylindrical roller bearings (DE), ball (NDE)
> 1000 kW Cylindrical roller bearings (both ends)

L10 life per ISO 281:

\[L_{10} = \left(\frac{C}{P}\right)^p \times \frac{10^6}{60 \times n}\]

where $C$ is dynamic bearing capacity, $P$ is equivalent load, $p$ = 3 for ball or 10/3 for roller, $n$ is speed in RPM. IEEE 841 requires minimum L10 of 3 years (26,280 hours) continuous operation.

5. Vibration Analysis (IEC 60034-14 / ISO 10816-3)

IEC 60034-14 Grade A limits (maximum vibration velocity at bearing housing):

Power Range Max. Vibration (mm/s RMS)
0.16 – 15 kW 1.6
15 – 75 kW 2.5
75 – 300 kW 3.5
> 300 kW 4.5

ISO 10816-3 classifies the operating condition into zones:

Zone Condition Action
A New machine Normal operation
B Long-term acceptable No action needed
C Short-term acceptable Plan corrective action
D Damaging Immediate shutdown

6. Noise Assessment (IEC 60034-9 / NORSOK S-002)

Sound power level limits depend on motor power and pole count per IEC 60034-9.

NORSOK S-002 workplace limit: 83 dB(A) at 1 m from equipment.

Sound pressure at 1 m is estimated from sound power level:

\[L_p = L_w - 10 \log_{10}(2 \pi r^2) \approx L_w - 8 \; \text{dB}\]

Note: Motors with VFD may produce 3–8 dB(A) additional noise from switching harmonics in the winding. This is flagged in design notes.

7. Enclosure and Protection (IEC 60034-5 / IEC 60079)

Zone IP Rating Ex Protection Enclosure Type
Safe area IP55 TEFC
Zone 2 IP55 Ex nA (non-sparking) TEFC
Zone 1 IP55 Ex d (flameproof) Flameproof
Zone 0 IP66 Ex d (flameproof) Flameproof, enhanced

API Reference

MotorMechanicalDesign

Package: neqsim.process.mechanicaldesign.motor

Constructors

Constructor Description
MotorMechanicalDesign() Default — set shaft power via setter
MotorMechanicalDesign(double shaftPowerKW) From known shaft power
MotorMechanicalDesign(ElectricalDesign elecDesign) From electrical design (reads motor params)

Configuration Methods

Method Parameters Description
setPoles(int) 2, 4, 6, 8 Motor pole count (default: 4)
setAmbientTemperatureC(double) °C Ambient temperature (default: 40)
setAltitudeM(double) meters Installation altitude (default: 0)
setHazardousZone(int) -1, 0, 1, 2 Hazardous zone (-1 = safe)
setGasGroup(String) IIA, IIB, IIC Gas group for Ex rating
setMotorStandard(String) IEC, NEMA Motor frame standard
setHasVFD(boolean) Whether motor has VFD

Design and Output Methods

Method Returns Description
calcDesign() void Run all design calculations
toJson() String Comprehensive JSON report
toMap() Map Design data as ordered map

Result Getters

Method Unit Description
getMotorWeightKg() kg Estimated motor weight
getTotalFoundationLoadKN() kN Static + dynamic foundation load
getRequiredFoundationMassKg() kg Minimum foundation mass (IEEE 841)
getFoundationType() Recommended foundation type
getCoolingCode() IEC 60034-6 IC code
getHeatDissipationKW() kW Motor heat loss
getBearingType() Ball or roller bearing type
getBearingL10LifeHours() hours ISO 281 L10 bearing life
getVibrationZone() ISO 10816-3 zone (A/B/C/D)
getMaxVibrationMmS() mm/s RMS IEC 60034-14 Grade A limit
getSoundPressureLevelAt1mDbA() dB(A) Sound pressure at 1 m
isNoiseWithinNorsokLimit() boolean True if ≤ 83 dB(A) at 1 m
getCombinedDeratingFactor() 0–1 Altitude × temperature derating
getDeratedPowerKW() kW Available power after derating
getIpRating() IP protection rating
getExMarking() Ex marking string (if hazardous)
getAppliedStandards() List Standards applied in design
getDesignNotes() List Warnings and recommendations

EquipmentDesignReport

A general-purpose class that generates a combined design report for any process equipment, aggregating mechanical design, electrical design, and motor mechanical design into a single JSON report with a feasibility verdict.

Package: neqsim.process.mechanicaldesign

Quick Start

Compressor comp = new Compressor("export", feed);
comp.setOutletPressure(80.0);
comp.run();

EquipmentDesignReport report = new EquipmentDesignReport(comp);
report.setUseVFD(true);
report.setRatedVoltageV(6600);
report.setHazardousZone(1);
report.setAmbientTemperatureC(45.0);
report.setAltitudeM(500.0);
report.generateReport();

System.out.println("Verdict: " + report.getVerdict());
System.out.println(report.toJson());

Configuration

Method Default Description
setUseVFD(boolean) false Whether to use a variable frequency drive
setRatedVoltageV(double) 400 Supply voltage (V)
setFrequencyHz(double) 50 Supply frequency (Hz)
setHazardousZone(int) -1 Hazardous area zone (-1 = safe, 0, 1, 2)
setGasGroup(String) IIA Gas group for Ex classification
setAmbientTemperatureC(double) 40 Ambient temperature (°C)
setAltitudeM(double) 0 Installation altitude (m)
setMotorStandard(String) IEC Motor standard (IEC or NEMA)
setMotorPoles(int) 4 Motor pole count
setMotorSizingMargin(double) 1.10 Motor sizing margin (10%)
setCableLengthM(double) 50 Cable length MCC to motor (m)

Verdict Logic

The report evaluates all design results and produces one of three verdicts:

Verdict Meaning
FEASIBLE All checks pass
FEASIBLE_WITH_WARNINGS Design possible but has warnings (noise, derating, oversizing)
NOT_FEASIBLE Blocking issue found (motor undersized)

Issues checked:

JSON Output Structure

{
  "equipmentName": "export",
  "equipmentType": "Compressor",
  "verdict": "FEASIBLE_WITH_WARNINGS",
  "issues": ["WARNING: ..."],
  "mechanicalDesign": { ... },
  "electricalDesign": {
    "shaftPowerKW": 450.0,
    "electricalInputKW": 495.0,
    "motor": { ... },
    "vfd": { ... },
    "powerCable": { ... },
    "switchgear": { ... },
    "hazardousArea": { ... }
  },
  "motorMechanicalDesign": {
    "designInput": { "shaftPowerKW": 450.0, ... },
    "derating": { "combinedDeratingFactor": 0.95, ... },
    "foundation": { "totalLoadKN": 25.3, ... },
    "vibration": { "vibrationZone_ISO10816": "A", ... },
    "cooling": { "coolingCode_IEC60034_6": "IC611", ... },
    "bearings": { "L10LifeHours": 52000, ... },
    "noise": { "soundPressureAt1mDbA": 81.5, ... },
    "enclosure": { "ipRating": "IP55", "exMarking": "Ex d IIA T3 Gb" },
    "appliedStandards": [ ... ]
  }
}

Load List Integration

Use toLoadListEntry() to get a summary suitable for an electrical load list:

Map<String, Object> entry = report.toLoadListEntry();
// Returns: equipmentName, ratedMotorPowerKW, absorbedPowerKW,
//          electricalInputKW, apparentPowerKVA, powerFactor, ratedVoltageV, hasVFD

Integration Workflow

The typical workflow for a complete equipment design is:

  1. Run the process simulation — sizes the equipment thermodynamically
  2. Mechanical design — wall thickness, weights, materials (via getMechanicalDesign())
  3. Electrical design — motor, VFD, cable, switchgear (via getElectricalDesign())
  4. Motor mechanical design — foundation, vibration, cooling, bearings, noise
  5. Combined reportEquipmentDesignReport aggregates all three into one
// Step 1: Process simulation
Compressor comp = new Compressor("HP Compressor", feed);
comp.setOutletPressure(100.0);
ProcessSystem process = new ProcessSystem();
process.add(feed);
process.add(comp);
process.run();

// Steps 2-5: Combined report handles everything
EquipmentDesignReport report = new EquipmentDesignReport(comp);
report.setUseVFD(true);
report.setRatedVoltageV(6600);
report.setHazardousZone(1);
report.setGasGroup("IIA");
report.setAmbientTemperatureC(45.0);
report.generateReport();

// Access individual designs
MechanicalDesign mech = report.getMechanicalDesign();
ElectricalDesign elec = report.getElectricalDesign();
MotorMechanicalDesign motor = report.getMotorMechanicalDesign();

// Full JSON report
String json = report.toJson();