Closed-loop SIF verification

ClosedLoopSafetyFunction connects process signals to redundant channels, a voting pattern, a logic-solver delay, and existing ProcessLogic final elements. Run it through DynamicSafetyScenarioRunner to verify the complete detection-to-safe-state path against an isolated copy of a ProcessSystem.

This workflow produces simulation evidence for engineering review. It does not assign SIL, approve an SRS, establish IPL independence, or replace project validation and functional-safety assessment. Those lifecycle activities remain controlled engineering decisions under IEC 61511.

Execution model

  1. The runner copies and initializes the design process.
  2. The initiating event is applied only to the copy.
  3. Each channel reads a live process signal and applies its trip direction, response delay, and explicit fault mode.
  4. The configured VotingPattern evaluates the latched channel trips.
  5. After the logic-solver delay, the supplied ESD, HIPPS, or other ProcessLogic executes.
  6. Dynamic criteria observe the physical process and final elements until their deadlines.
  7. The result records channel traces, vote time, actuation time, final state, and criteria verdicts.

2oo3 high-pressure isolation example

DynamicSafetyScenario scenario = DynamicSafetyScenario
    .builder("SIF-HP-101", "HP inlet isolation")
    .durationSeconds(8.0)
    .timeStepSeconds(0.25)
    .initiatingEvent(process ->
        ((Stream) process.getUnit("FEED")).setPressure(70.0, "bara"))
    .addLogic(process -> {
      ESDValve valve = (ESDValve) process.getUnit("ESDV-101");
      ESDLogic finalElements = new ESDLogic("ESD-101 final elements");
      finalElements.addAction(new TripValveAction(valve), 0.0);

      SafetyFunctionChannel.SignalExtractor pressure = model ->
          ((Stream) model.getUnit("FEED")).getPressure("bara");
      return ClosedLoopSafetyFunction
          .builder("SIF-HP-101", "2oo3 HP isolation", process,
              VotingPattern.TWO_OUT_OF_THREE, finalElements)
          .addChannel(SafetyFunctionChannel
              .highTrip("PT-101A", "bara", 60.0, pressure)
              .responseDelaySeconds(0.5).build())
          .addChannel(SafetyFunctionChannel
              .highTrip("PT-101B", "bara", 60.0, pressure)
              .responseDelaySeconds(0.5).build())
          .addChannel(SafetyFunctionChannel
              .highTrip("PT-101C", "bara", 60.0, pressure)
              .responseDelaySeconds(0.5)
              .faultMode(SafetyFunctionChannel.FaultMode.BYPASSED).build())
          .logicSolverDelaySeconds(0.25)
          .build();
    })
    .addCriterion(DynamicScenarioCriterion
        .builder("esdv-closed", "ESD valve closed", "%", process ->
            ((ESDValve) process.getUnit("ESDV-101"))
                .getPercentValveOpening())
        .acceptanceRange(null, 5.0)
        .deadlineSeconds(5.0)
        .build())
    .addEvidenceReference("SRS-SIF-HP-101")
    .build();

DynamicSafetyScenarioResult result =
    DynamicSafetyScenarioRunner.run(designProcess, scenario);
Map<String, Object> sifEvidence =
    result.getLogicEvidence().get("2oo3 HP isolation");

The example intentionally bypasses one channel. The 2oo3 vote still requires two demanded channels, and the evidence exposes the reduced availability for review. A bypass is never treated as proof that operation in the degraded state is acceptable.

Channel fault modes

Mode Simulation behavior Intended verification use
HEALTHY Uses the process signal Normal demand test
BYPASSED Channel unavailable and cannot vote Authorized-bypass scenario
STUCK_NORMAL Never demands a trip Dangerous detected/undetected failure scenario
STUCK_TRIP Always demands a trip Spurious-trip and voting scenario
BIASED Adds a configured bias to the process signal Calibration-drift sensitivity

Evidence and acceptance

The dynamic_safety_scenario_result.v2 JSON contains logicEvidence alongside the existing criterion traces and final logic states. Closed-loop evidence uses closed_loop_sif_evidence.v1 and includes:

Define criteria from the SRS response-time and safe-state requirements. Use sufficiently small time steps to resolve sensor, logic, and actuator dynamics, and test normal demand, each credited degraded mode, reset/restart behavior, and failure to reach the safe state.

Standards context

Project requirements, vendor data, cause-and-effect charts, proof-test procedures, and approved SRS values take precedence over screening examples in NeqSim.