Closed-loop SIF verification

Connected PSV response alongside shutdown

The opt-in AdvancedV101PsvStudy extends the two-inventory example with an actual native SafetyReliefValve branch, leaving the original 23 cases unchanged. See its tested public model contract for the native tee/valve/disposal topology, ten profiles, four timestep refinements, fault overrides and numerical gates. The PSV is passive self-action, not an invented SIF or a software pressure transmitter.

The opt-in gas-service study explicitly enables native choking on inlet ESD, HIPPS, PCV and PSV, including gas-valve design-point calibration. A frozen synthetic Cv 40/80/120 comparison retains the capped Cv 40 pressure failure and selects Cv 80 as the smallest passing tested alternative; its half-timestep verification uses the same pressure and energy criteria. Uncapped checkpoints are preserved as superseded evidence, not credited pressure protection. This is not vendor relief sizing.

Use the corrected UUID runtime: both steady and transient entry points execute the PSV law and parent native Cv capacity applies lift once. SNAP commands opening at set pressure, with reseat hysteresis; the modulating alternatives are explicitly unlatched/latched synthetic curves. A stable-command floor must not override physical rate limits or prevent exact seating. A pressure boundary with zero specified demand uses temporary intensive-property normalization; actual computed flow replaces it, and closure/no-forward-pressure/failure leaves exact zero ports. Ordinary cold ThrottlingValve behavior is unchanged. Complete response snapshots and explicit legacy serialized model migration are required; stored closure parameters alone are not execution evidence.

The connected branch must refresh current intensive state, solve each real valve and aggregate the actual demands before the vessel consumes withdrawal. Record pressure, actual lift and discharge, backpressure, pop/reseat chronology and per-vessel conservation separately. Functioning shutdown can keep the PSV on standby; a stuck-open PSV can fail unwanted-relief requirements while pressure remains below its upper limit. Retain these distinct scopes and expected native FAILs.

These are synthetic Cv response studies and traceable P&ID inputs. They do not certify vendor capacity, API/ISO relief sizing, SIL or construction. Fixed backpressure is not a simulated flare header. Numerical energy FAIL/INCOMPLETE and whole-train transaction limitations retain qualification HOLD.

ClosedLoopSafetyFunction connects process signals to redundant channels, a voting pattern, a logic-solver delay, and existing ProcessLogic final elements. Run it through DynamicSafetyScenarioRunner to verify the complete detection-to-safe-state path against an isolated copy of a ProcessSystem.

This workflow produces simulation evidence for engineering review. It does not assign SIL, approve an SRS, establish IPL independence, or replace project validation and functional-safety assessment. Those lifecycle activities remain controlled engineering decisions under IEC 61511.

Execution model

  1. The runner copies and initializes the design process.
  2. The initiating event is applied only to the copy.
  3. Each channel reads its configured input and applies its trip direction, response qualification, and explicit fault mode. Measurement-backed channels read the native held sample without advancing the instrument signal chain again.
  4. The configured VotingPattern evaluates the latched channel trips.
  5. After the logic-solver delay, the supplied ESD, HIPPS, or other ProcessLogic executes.
  6. Dynamic criteria observe the physical process and final elements until their deadlines.
  7. The result records channel traces, vote time, actuation time, final state, and criteria verdicts.

Event-exact timing policy

The default runner policy remains LEGACY_FIXED_SCAN for compatibility. For quantitative response-time verification, opt in with .eventExactTiming(true). The event-exact policy:

The policy does not interpolate inside a sensor, logic-solver, or actuator scan. Choose a scan interval that resolves the shortest declared response time and repeat at a smaller interval. In the public 0.25 s synthetic 2oo3 case, two healthy 1.0 s channels vote at 1.0 s, the 0.5 s logic delay actuates at 1.5 s, and the 2.0 s ESD-valve stroke reaches the closed criterion at 3.5 s. Replacing one healthy channel by STUCK_NORMAL while another is bypassed leaves the scenario FAIL with no vote or actuation timestamp. These are executable software-timing checks, not vendor response data or safety credit.

Actual inputs, fixed voting and lifecycle

Use SafetyFunctionChannel.highTripFromMeasurement(...) or lowTripFromMeasurement(...) for a registered instrument with enabled native transient sampling. The factory derives the channel tag from the actual measurement object and rejects a reference captured from another process copy. manualTripFromPushButton(...) reads an actual local, unlinked native PushButton. Legacy custom extractors remain supported but their configuration identity is explicitly unverified. Create fresh logic from the executing isolated process in each scenario’s factory.

ClosedLoopSafetyFunction rejects duplicate channel objects and duplicate normalized channel tags before evaluation. getChannels() returns an unmodifiable list containing the actual input objects; getFinalElementLogic() returns the actual configured native logic. These identity checks prevent counting one configured input twice; they do not prove independent field sensing or common-cause coverage.

Response delay qualifies continuous demand on held scalar samples. Once qualified, each native channel latches until reset. Nonoverlapping qualified pulses can therefore accumulate a 2oo3 vote. Bypass retains the configured m-out-of-n requirement and does not silently select a degraded pattern. Specify and test whether these semantics meet the intended SRS.

Pausing and reactivating resumes the same qualification, vote and final-element progress. A pre-vote pause does not command a final element; a failed child is not restarted by parent resume. Reset clears bookkeeping and invokes the child reset once. It is not an operating permissive and does not reopen physical isolation. The public reset/retrip study separately checks current indicated conditions, preserves the first native trace epoch, and requires an explicit operator rearm and reopening.

Full sampled windows and strict project evidence

The default criterion remains REACH_BY_DEADLINE. It proves a target was reached and cannot prove that a pressure upper limit or no-trip requirement held throughout a scenario. Use MAINTAIN_BOUNDS with a positive deadline equal to the complete intended event window. Its native result requires start/end sample coverage, checks every sample, and reports the first violation and observed extrema. It does not establish behavior between scans.

For a governed engineering project, EngineeringSimulationRunner.runStrict(project) records the results of direct strict execution on that project’s frozen scenarios. Preserve definition IDs, canonical PID revision, actual-input/action readback and evidence references before this execution. Do not attach unrelated same-name results as proof of the configured project.

Two-inventory advanced study

The executable AdvancedV101SafetyStudy and its tests use real V100/V101 separator inventories, three BPCS PI loops, two distinct finite-stroke isolation valves, 1oo2 ESD, a 2oo3 HIPPS candidate and a manual parallel trip. There are 17 registered measurement devices: 16 held instruments and one discrete push button. The public study contract documents the feed, geometry, boundaries, tags, actual scan order and all 18 profiles. The executed study matrix contains those 18 cases at 0.1 s plus five 0.05 s refinement cases. Actual physical step UUIDs and durations are read from ProcessSystem, including tiny final alignment steps; they must not be reconstructed by rounding wall time divided by nominal dt.

The matrix retains healthy and no-demand cases, one/two false-high or stuck inputs, bypass, failed/slow actuators, inhibited protection, manual trip, pause, asynchronous latched pulses and reset/retrip. A JUnit PASS can assert an expected native simulation FAIL. Command times and each valve’s actual closure are separate evidence; backup ESD action does not satisfy a required HIPPS closure.

The nominal stroke and trip settings are synthetic model inputs. The HIPPS candidate uses actual native ESDValve travel; legacy HIPPS immediate commands and closure-time metadata are not travel evidence. No sensor-independence, SIL or independent-layer credit follows from distinct model tags.

Keep response, numerical conservation and engineering qualification separate. The frozen per-vessel cumulative energy limit is 1e-5 of absolute initialized internal energy. The upstream inventory’s energy FAIL remains a FAIL even where pressure response passes or whole-slice debts partly cancel. Require complete native coverage and an independent audit of the ordered consumed mass/component/ enthalpy boundaries. The advanced study remains qualification HOLD; the numerical criterion is not relaxed.

Final-element availability and traceability

ESDValve is available by default. Set setActuatorAvailable(false) only when a declared unavailable-actuator or mechanically stuck case must hold the valve at its current position after a shutdown demand. The solenoid and trip logic still change state, so the result distinguishes a missing demand from a demanded final element that cannot travel. Use setStrokeTime(...) for a slow but moving case; do not represent slow travel by clipping the position or by treating an unavailable valve as closed.

Attach controlled identities to each executable case with addRequirementId(...) and addEquipmentTag(...). The scenario and dynamic_safety_scenario_result.v2 retain these values in insertion order, providing a stable requirement-to-tag-to-scenario-to-result join for study reports. The runner does not infer approval or safety credit from these identifiers. When a scenario belongs to an EngineeringProject, EngineeringProject.validate() checks that every requirement identifier exists and that every exercised tag resolves to process equipment, a stream, or a measurement device. Give the case configuration, initiating event, each logic factory, and each criterion extractor stable definition-and-revision identifiers through the overloads that accept a definition ID. Change that ID whenever the callback behavior or its controlled source revision changes. Legacy overloads remain available but are exported as UNSPECIFIED and produce the ENG-DYNAMIC-006 review finding. Unregistered evidence references remain review findings rather than simulated proof of an approved SRS, P&ID, instrument index, or cause-and-effect chart.

The public regression matrix uses the same 1.0 s sensor delay and 0.5 s logic delay for every case:

Final-element case Declared behavior First safe position 3.5 s deadline
Healthy 2.0 s full stroke 3.5 s PASS
Slow 4.0 s full stroke 5.5 s FAIL
Unavailable demanded, no travel not reached FAIL

The 0.25 s and 0.125 s scans both resolve the healthy safe-position time at 3.5 s. Rejected transient trials and serialized restart preserve the availability flag. These values qualify the synthetic software case only; use reviewed vendor stroke data, utility architecture, site test data, and project response-time requirements for engineering decisions.

Revision-controlled scenario evidence

After EngineeringSimulationRunner executes a project, the project retains the latest coordinated result as transient run evidence. EngineeringGraphBuilder then materializes two stable identities for each case:

The result node is GENERATED_FROM the scenario node. Consequently, a changed public scenario definition propagates revision impact to its result, while a changed quantitative result can invalidate only the result. EngineeringApprovalLedger reports existing approvals as REVALIDATION_REQUIRED for the affected node(s); it never silently carries approval across a changed executable definition or result. The latest result is transient: rerun the coordinated simulation before compiling an evidence graph after restart or deserialization.

Persisted graph snapshots retain the number representations in nested scenario evidence, including integer logic counters. Reloading an unchanged snapshot preserves its fingerprint and produces no revision impact; changing stored evidence without updating the fingerprint is rejected during graph reconstruction.

Controlled definition IDs are project-governed identities, not hashes of callback bytecode. Configuration control must change an ID when implementation behavior changes and rerun the scenario before review.

This graph contract records simulation evidence and review state. It does not approve the scenario, assign SIL or IPL credit, or establish detector coverage, voting independence, vendor response, or site acceptance.

2oo3 high-pressure isolation example

DynamicSafetyScenario scenario = DynamicSafetyScenario
    .builder("SIF-HP-101", "HP inlet isolation")
    .durationSeconds(8.0)
    .timeStepSeconds(0.25)
    .initiatingEvent("feed-high-pressure-v1", process ->
        ((Stream) process.getUnit("FEED")).setPressure(70.0, "bara"))
    .addLogic("sif-hp-101-2oo3-v1", process -> {
      ESDValve valve = (ESDValve) process.getUnit("ESDV-101");
      ESDLogic finalElements = new ESDLogic("ESD-101 final elements");
      finalElements.addAction(new TripValveAction(valve), 0.0);

      SafetyFunctionChannel.SignalExtractor pressure = model ->
          ((Stream) model.getUnit("FEED")).getPressure("bara");
      return ClosedLoopSafetyFunction
          .builder("SIF-HP-101", "2oo3 HP isolation", process,
              VotingPattern.TWO_OUT_OF_THREE, finalElements)
          .addChannel(SafetyFunctionChannel
              .highTrip("PT-101A", "bara", 60.0, pressure)
              .responseDelaySeconds(0.5).build())
          .addChannel(SafetyFunctionChannel
              .highTrip("PT-101B", "bara", 60.0, pressure)
              .responseDelaySeconds(0.5).build())
          .addChannel(SafetyFunctionChannel
              .highTrip("PT-101C", "bara", 60.0, pressure)
              .responseDelaySeconds(0.5)
              .faultMode(SafetyFunctionChannel.FaultMode.BYPASSED).build())
          .logicSolverDelaySeconds(0.25)
          .build();
    })
    .addCriterion(DynamicScenarioCriterion
        .builder("esdv-closed", "ESD valve closed", "%",
            "esdv-101-opening-percent-v1", process ->
            ((ESDValve) process.getUnit("ESDV-101"))
                .getPercentValveOpening())
        .acceptanceRange(null, 5.0)
        .deadlineSeconds(5.0)
        .build())
    .addRequirementId("REQ-SIF-HP-101")
    .addEquipmentTag("PT-101A")
    .addEquipmentTag("PT-101B")
    .addEquipmentTag("PT-101C")
    .addEquipmentTag("ESDV-101")
    .addEvidenceReference("SRS-SIF-HP-101")
    .build();

DynamicSafetyScenarioResult result =
    DynamicSafetyScenarioRunner.run(designProcess, scenario);
Map<String, Object> sifEvidence =
    result.getLogicEvidence().get("2oo3 HP isolation");

The example intentionally bypasses one channel. The 2oo3 vote still requires two demanded channels, and the evidence exposes the reduced availability for review. A bypass is never treated as proof that operation in the degraded state is acceptable.

Channel fault modes

Mode Simulation behavior Intended verification use
HEALTHY Uses the process signal Normal demand test
BYPASSED Channel unavailable and cannot vote Authorized-bypass scenario
STUCK_NORMAL Never demands a trip Dangerous detected/undetected failure scenario
STUCK_TRIP Always demands a trip Spurious-trip and voting scenario
BIASED Adds a configured bias to the process signal Calibration-drift sensitivity

Evidence and acceptance

The dynamic_safety_scenario_result.v2 JSON contains logicEvidence alongside the existing criterion traces and final logic states. Closed-loop evidence uses closed_loop_sif_evidence.v1 and includes:

Define criteria from the SRS response-time and safe-state requirements. Use sufficiently small time steps to resolve sensor, logic, and actuator dynamics, and test normal demand, each credited degraded mode, reset/restart behavior, and failure to reach the safe state.

Standards context

Project requirements, vendor data, cause-and-effect charts, proof-test procedures, and approved SRS values take precedence over screening examples in NeqSim.