SIF reliability uncertainty and degraded modes

SafetyFunctionDesign remains the analytical source for low-demand PFDavg and high/continuous-demand PFH screening. Two complementary APIs add lifecycle evidence without changing or certifying that model:

Neither result infers a SIL target, authorizes continued operation, validates common-cause independence, or replaces a project SIL verification. Every output sets engineeringApprovalRequired.

Reliability uncertainty

Define triangular distributions only where the project has an evidence basis. Failure-rate, proof-test, and repair-time distributions are factors on the controlled design values. Diagnostic coverage, beta, and bypass probability distributions are absolute fractions.

SafetyFunctionReliabilityStudy.SubsystemUncertainty sensors =
    new SafetyFunctionReliabilityStudy.SubsystemUncertainty("2oo3 pressure transmitters")
        .setFailureRateFactor(TriangularDistribution.of(0.8, 1.0, 1.3))
        .setDiagnosticCoverage(TriangularDistribution.of(0.55, 0.60, 0.65))
        .setProofTestIntervalFactor(TriangularDistribution.of(0.9, 1.0, 1.2))
        .setBetaFactor(TriangularDistribution.of(0.03, 0.05, 0.08));

SafetyFunctionReliabilityStudy.Result reliability =
    SafetyFunctionReliabilityStudy.run(
        safetyFunctionDesign, Collections.singletonList(sensors), 10000, 20260718L);

Store the seed, iteration count, distributions, data sources, and deterministic design result together. P10 is the lower PFD/PFH percentile and P90 is the higher, more conservative percentile. Do not select only a favorable percentile to claim compliance; the acceptance basis belongs in the approved SRS and verification plan.

Degraded and maintenance operation

An operating-mode snapshot uses one-based channel numbers and exact subsystem names from SafetyFunctionDesign:

SafetyFunctionOperatingMode mode = SafetyFunctionOperatingMode
    .builder("PT-C authorized bypass", ModeType.DEGRADED)
    .authorizationReference("OPS-BYPASS-2026-014")
    .compensatingMeasure("Continuous pressure watch and restricted throughput")
    .duration(2.0, 8.0)
    .channelState("2oo3 pressure transmitters", 3, ChannelState.BYPASSED)
    .hoursSinceProofTest("2oo3 pressure transmitters", 4000.0)
    .build();

SafetyFunctionDegradedModeAssessment.Result assessment =
    SafetyFunctionDegradedModeAssessment.assess(safetyFunctionDesign, mode);

For a 2oo3 group with one bypassed channel, the result reports effective 2oo2: demand capability remains, but redundancy and the original SIL claim are not preserved by this screen. Two unavailable channels produce 2oo1 and NOT_DEMAND_CAPABLE. A forced-trip channel reduces the remaining vote and exposes spurious-trip susceptibility.

Non-normal modes are flagged unless they include an authorization reference, compensating measure, and maximum duration. Exceeding the duration is a finding. Proof-test age must be recorded for every subsystem; overdue or missing evidence invalidates preservation of the design claim.

Required review package

See the official IEC 61511-1 lifecycle requirements and IEC 61511-2 application guidance for the governing project context.