The repository includes an alarm-to-process-logic demonstration at src/test/java/neqsim/process/util/example/ProcessLogicAlarmIntegratedExample.java. It is test-source software for exploring API interactions and scenario sequencing. It is not a qualified design basis, a reusable industrial safeguard, or evidence that a protective function meets a required integrity level.

For a smaller, documentation-tested alarm lifecycle example, start with Alarm Configuration and Lifecycle.

What the demonstration shows

The test-source program assembles a simulated process, measurement devices, alarm configurations, ProcessAlarmManager, and process-logic objects. Its scenarios illustrate these software interactions:

Demonstrated interaction What can be inspected
Threshold evaluation Alarm events created from simulated measurements
Handler registration A matching alarm event can invoke an AlarmActionHandler
Process-logic activation A handler can activate a modeled logic object
Acknowledgement and history Alarm state and generated events can be collected for review
Scenario sequencing Input conditions can be changed between simulation steps

The numeric setpoints, delays, deadbands, valve actions, and scenario order are illustrative values embedded in a test example. They are not recommendations for a plant or project.

Important voting limitation

The source describes three pressure transmitters in its HIPPS-style scenario, but the manager registers an independent HIHI handler for each transmitter. Each matching transmitter event can activate the same logic object. The demonstration therefore does not implement or prove two-out-of-three voting at the alarm-manager layer.

Before describing a modeled function as a voting architecture, implement and test explicit vote collection, coincidence timing, channel health, degraded-mode behavior, reset rules, bypass handling, and common-cause assumptions. Review the resulting logic independently from the prose that describes it.

What is not established

The demonstration does not establish:

An alarm threshold and an automatic callback are software mechanisms. They must not be counted as independent or credited safeguards without the project-specific hazard analysis, requirements, architecture, verification, and approval that support that claim.

Safe use in engineering studies

Use the demonstration as a starting point for software exploration only. For an engineering study:

  1. derive alarm and trip requirements from the approved hazard and operability assessment and risk analysis;
  2. separate operator alarms, basic process control actions, and protective functions in the requirements and model;
  3. document independence and common-cause assumptions for every claimed protection layer;
  4. implement voting and state transitions explicitly, with deterministic unit and integration tests;
  5. validate dynamic response using justified process cases and uncertainty assumptions; and
  6. preserve traceability from each requirement to configuration, code, test evidence, and review approval.

Run the class from test sources only when you need to inspect the current demonstration:

./mvnw -Dexec.classpathScope=test -Dexec.mainClass="neqsim.process.util.example.ProcessLogicAlarmIntegratedExample" exec:java

Execution confirms only the behavior of that source revision in the selected environment. It does not qualify the modeled safeguards.