HIPPSLogic is a logic-centric simulation component. It evaluates explicit detector values, changes its own state, and commands a linked ThrottlingValve. This page documents current software behavior and the evidence a project must add before using the result in a safety decision.

For API selection and the equipment-centric alternative, start with HIPPS Modeling Boundary.

Construction and identity

Construct HIPPSLogic(String, VotingLogic) with a stable project tag and the neqsim.process.logic.sis.VotingLogic enum. That enum defines required votes and total channels for 1oo1, 1oo2, 2oo2, 2oo3, 2oo4, and 3oo4 patterns.

Add no more than the enum’s declared channel count with addPressureSensor(Detector). Detector stores its type, alarm level, numerical set point, and unit text. The caller is responsible for converting each update value to the declared unit and for retaining source and calibration context.

Connect the final element with setIsolationValve(ThrottlingValve). The reference is optional in software, but a trip without a linked valve cannot isolate a modeled stream.

Voting and trip transition

update(double...) requires exactly one value per configured detector. Each detector updates before the voting condition is evaluated.

The current evaluation order is:

  1. If logic override is active, return without evaluating.
  2. Count bypassed and faulty detectors.
  3. Enter FAILED when their combined count exceeds the model’s allowed count.
  4. Count tripped detectors that are neither bypassed nor faulty.
  5. Evaluate the configured VotingLogic.
  6. On the first satisfied vote, set the logic to tripped and RUNNING, then command the linked valve to zero-percent opening.

This is a deterministic software transition. It does not establish detector independence, diagnostic coverage, common-cause behavior, final-element capacity, or process-response adequacy.

Time and escalation

execute(double) advances timeSinceTrip in seconds only after the logic has tripped and while override is not active.

linkToEscalationLogic(ProcessLogic, double) stores a secondary logic and a delay. After the delay, execute(double) recounts tripped sensors and calls activate() on the secondary logic if the vote remains satisfied. The model does not verify that the secondary layer is independent or that the delay is suitable.

setValveClosureTime(double) stores a target on HIPPSLogic; current HIPPSLogic trip behavior commands zero opening immediately. Do not interpret the stored target as a simulated actuator travel profile. Model the linked valve and process transient explicitly when closure dynamics matter.

Override, fault, and bypass behavior

setOverride(true) inhibits voting and execution and changes the logic state to PAUSED. Clearing override returns the state to RUNNING if already tripped or IDLE otherwise.

A bypassed or faulty Detector does not contribute a trip vote. If degraded channels exceed the internal allowance, HIPPSLogic reports FAILED. These flags are scenario inputs; the class does not enforce a project bypass permit, compensating measure, proof-test workflow, or operating time limit.

Treat override and bypass scenarios as explicit, reviewed cases. Never use these software switches as plant commands or evidence of operating authorization.

Reset behavior

reset() returns false while any detector remains tripped. After all detectors clear, a successful reset:

The reopening is a simulation convenience. It is not a real reset permissive, operator authorization, or safe restart sequence. A project model that evaluates restart must represent process conditions, permissives, actuator state, and approval separately.

deactivate() does not reset HIPPSLogic, and isComplete() remains false because the object represents continuously available monitoring rather than a finite sequence.

Evidence to retain

For each scenario, retain at least:

Use the enabled ProcessSafetyOverviewDocumentationTest as source-linked executable evidence for the public HIPPSLogic surface. Use HIPPSValveTest only for the separate equipment-centric API.

Qualification boundary

Voting notation and state transitions are not a SIL calculation. Configuration does not demonstrate SIL achievement. The model does not certify IEC 61508 or IEC 61511 compliance, protection-layer independence, proof-test effectiveness, or relief credit. Trip thresholds, response times, degradation rules, and acceptance criteria must be project-specific and require independent functional-safety assessment and accountable approval.

See Implementing HIPPS Models and the maintained safety quick start for the wider simulation workflow.