HIPPSLogic is a logic-centric simulation component. It evaluates explicit detector values, changes its own state, and commands a linked ThrottlingValve. This page documents current software behavior and the evidence a project must add before using the result in a safety decision.

For API selection and the equipment-centric alternative, start with HIPPS Modeling Boundary.

Construction and identity

Construct HIPPSLogic(String, VotingLogic) with a stable project tag and the neqsim.process.logic.sis.VotingLogic enum. That enum defines required votes and total channels for 1oo1, 1oo2, 2oo2, 2oo3, 2oo4, and 3oo4 patterns.

Add no more than the enum’s declared channel count with addPressureSensor(Detector). Detector stores its type, alarm level, numerical set point, and unit text. The caller is responsible for converting each update value to the declared unit and for retaining source and calibration context.

Connect the final element with setIsolationValve(ThrottlingValve). The reference is optional in software, but a trip without a linked valve cannot isolate a modeled stream.

Voting and trip transition

update(double...) requires exactly one value per configured detector. Each detector updates before the voting condition is evaluated.

A vote uses the current scan. Two high readings on different channels at different times cannot trip a 2oo3 solver. Individual detector alarm histories and the solver trip remain latched separately. Each distinct healthy detector contributes at most one vote. Missing, nonfinite, bypassed and faulty readings reduce voting capacity. An unavailable voting quorum gives a FAILED diagnostic. setTripOnLostVotingCapacity(true) also commands isolation on quorum loss. Choose this response explicitly for a project’s degraded-mode policy.

Time and escalation

Link the primary valve with setIsolationValve(ThrottlingValve) and additional valves with addIsolationValve(ThrottlingValve). Material streams or an explicit hydraulic boundary define the series connection. setValveClosureTime(double) configures the common stroke duration. Set an individual valve’s stroke after linking it to represent unequal actuators. A transient HIPPS valve latches a zero target. Its normal actuator step advances actual position; steady equipment uses the instantaneous position. A generic throttling valve receives the target and requires separate coordination of any competing controller commands.

linkToEscalationLogic(ProcessLogic, double) commands a secondary sequence once the current pressure vote stays high continuously for the configured delay. Call update at the start of each pressure scan, advance the plant and actuators over the interval, and call execute(dt) once for that interval. Clearing the vote restarts the escalation timer. Trapped gas can sustain a high pressure after the inlet seats, so record both valve positions and protected pressure when interpreting escalation.

Override, fault, and bypass behavior

Logic override inhibits new logic trips and escalation. Existing HIPPS valve latches continue to demand closure. A trip interrupts an active partial-stroke test. Model plant-specific override authorization, time limits and compensating measures in the operating procedure.

Reset behavior

Reset requires a full group of healthy, clear readings and cleared local valve pressure alarms. It releases the latch and leaves the isolation demand at zero. Reopening requires a separate command. On restart from old serialized logic, reconnect the pressure channels omitted by the old storage format.

deactivate() leaves the latch intact. isComplete() stays false for this continuously monitored function.

Evidence to retain

For each scenario, retain at least:

Use the enabled ProcessSafetyOverviewDocumentationTest as source-linked executable evidence for the public HIPPSLogic surface. Use HIPPSValveTest only for the separate equipment-centric API.

Qualification boundary

Voting notation and state transitions are not a SIL calculation. Configuration does not demonstrate SIL achievement. The model does not certify IEC 61508 or IEC 61511 compliance, protection-layer independence, proof-test effectiveness, or relief credit. Trip thresholds, response times, degradation rules, and acceptance criteria must be project-specific and require independent functional-safety assessment and accountable approval.

See Implementing HIPPS Models and the maintained safety quick start for the wider simulation workflow.