Executable operating procedures

OperatingProcedure turns an approved sequence into executable simulation logic without replacing native process equipment. Each step separates the requested command from measured completion, so a slow or stuck actuator cannot be credited merely because its command was issued.

Contract

Every procedure declares a stable ID, revision and name. Procedure-level and step-level prerequisites use existing LogicCondition implementations. A step also declares:

SetValveTargetAction changes ThrottlingValve.getTargetPercentValveOpening() and leaves measured position to the valve travel model. Rate limit, first-order lag, deadband, stiction and hysteresis therefore remain active. OperatingProcedureRunner advances the caller-supplied ProcessSystem with deterministic physical-step identities and returns timestamped JSON evidence.

valve.setTravelModel(ValveTravelModel.LINEAR_RATE_LIMIT);
valve.setTravelTime(4.0);

OperatingProcedure startup = new OperatingProcedure(
    "OPS-START-001", "A", "Open inlet isolation");
startup.addPrerequisite(new PressureCondition(feed, 10.0, ">"));
startup.addOperatorStep(
    "OPEN-SDV",
    null,
    new SetValveTargetAction(valve, 100.0, 0.5),
    new ValvePositionCondition(valve, ">=", 99.5, 0.5),
    8.0,
    new SetValveTargetAction(valve, 0.0, 0.5));

startup.activate();
startup.execute(0.0);
startup.authorizeOperatorStep("OPEN-SDV");

For automatic procedures, OperatingProcedureRunner.run(...) performs the activation and scan loop. Operator-owned procedures expose authorizeOperatorStep(...) so the caller can insert an operator action at a controlled scan. Authorization is accepted only for the current active operator-owned step; pre-authorization and a mismatched step ID fail explicitly. The execution record retains activation, readiness, step entry, operator wait/authorization, command, measured completion, recovery, first-out and terminal events with seconds, actual value and expected value.

Quantitative regression

The public regression uses a 20 bara methane/ethane feed, 10 bara downstream boundary and a native control valve with a four-second linear full stroke. A 0.5 s procedure scan reaches 100% measured position at 4.0 s; repeating at a 0.25 s scan preserves that completion time and final position. Repeating the 0.5 s procedure against an independently rebuilt starting state produces byte-identical JSON evidence. A 150 percentage-point synthetic stiction band holds the stem at 0%; the step times out at 2.0 s, records OPEN-SDV as first-out and issues its configured close recovery. An operator-owned restart without authorization records the wait, issues no open command and times out at 2.0 s. With authorization at the initial scan, the same operator-owned step issues its command once and confirms the 100% measured position at 4.0 s.

These are deterministic synthetic commissioning tests. They do not establish an approved procedure, operator competence, alarm rationalization, SIS independence, SIL, SRS, FAT/SAT, construction approval or operating approval. Project procedures must supply reviewed prerequisites, timeouts, valve data, recovery actions, command ownership and acceptance limits. A caller seeking restart must restore or reconstruct the required process snapshot and separately satisfy reset and restart permissives; the runner does not invent a safe state.