NeqSim provides stream-connected safety equipment, sequenced process logic, scenario runners, and screening utilities. These layers serve different purposes and should not be presented as one universal safety-design API.

Safety calculations are engineering evidence, not an approval. A project must still establish credible scenarios, design conditions, standards editions, safeguard independence, uncertainty, acceptance criteria, and accountable review.

Choose the correct layer

Need Current API Boundary
Model pressure-responsive or fail-safe equipment SafetyValve, RuptureDisk, ESDValve, BlowdownValve Constructors accept a StreamInterface, not a vessel object
Sequence shutdown actions ESDLogic with TripValveAction, ActivateBlowdownAction, and related actions Call activate() and advance both logic and equipment with the same time-step basis
Model HIPPS voting and final action HIPPSLogic, Detector, and VotingLogic Sensor quality, bypasses, proof testing, SIL claims, and independence require separate evidence
Produce structured transient evidence EmergencyShutdownTestRunner, DynamicSafetyScenarioRunner, and ClosedLoopSafetyFunction Define monitored tags, criteria, calculation identity, and result retention explicitly
Screen relief load and area ReliefValveSizing and the scenario definitions on SafetyValve Static sizing is separate from the valve’s dynamic opening and reseating behavior
Hand off consequence inputs Release, dispersion, open-drain, flare, and CFD source-term utilities Layout, weather, leak frequency, escalation, and QRA conclusions remain external qualification tasks

Units and state ownership

API Input meaning
SafetyValve.setPressureSpec(double) Absolute set pressure in bara
SafetyValve.setFullOpenPressure(double) Absolute fully-open pressure in bara
SafetyValve.setBlowdown(double) Reseating margin as percent below set pressure
RuptureDisk.setBurstPressure(double) Absolute burst pressure in bara
RuptureDisk.setFullOpenPressure(double) Absolute fully-open pressure in bara
ESDValve.setStrokeTime(double) Closure time in seconds
BlowdownValve.setOpeningTime(double) Opening time in seconds
runTransient(double, UUID) Time increment in seconds plus a stable calculation identity

The valve classes inherit unit-aware outlet-pressure methods from ThrottlingValve, for example setOutletPressure(1.5, "bara"). The device-specific set, burst, and full-open setters above do not accept a unit string. Convert project gauge-pressure values to absolute pressure before using those setters.

RuptureDisk.reset() exists to reset a simulation case. It does not imply that a ruptured physical disk can reseat or be returned to service.

Executable Java 8 quick start

This example configures pressure-protection devices and executes a fail-close/fail-open ESD sequence. It demonstrates API behavior; it does not size a relief device or validate a safety function.

import java.util.UUID;
import org.apache.logging.log4j.LogManager;
import org.apache.logging.log4j.Logger;
import neqsim.process.equipment.stream.Stream;
import neqsim.process.equipment.valve.BlowdownValve;
import neqsim.process.equipment.valve.ESDValve;
import neqsim.process.equipment.valve.RuptureDisk;
import neqsim.process.equipment.valve.SafetyValve;
import neqsim.process.logic.action.ActivateBlowdownAction;
import neqsim.process.logic.action.TripValveAction;
import neqsim.process.logic.esd.ESDLogic;
import neqsim.thermo.system.SystemInterface;
import neqsim.thermo.system.SystemSrkEos;

public final class ProcessSafetyOverviewQuickStart {
  private static final Logger logger =
      LogManager.getLogger(ProcessSafetyOverviewQuickStart.class);

  private ProcessSafetyOverviewQuickStart() {}

  public static void main(String[] args) {
    SystemInterface fluid = new SystemSrkEos(298.15, 80.0);
    fluid.addComponent("methane", 0.95);
    fluid.addComponent("ethane", 0.05);
    fluid.setMixingRule("classic");

    Stream feed = new Stream("safety feed", fluid);
    feed.setFlowRate(1000.0, "kg/hr");
    feed.run();

    SafetyValve safetyValve = new SafetyValve("PSV-100", feed);
    safetyValve.setPressureSpec(75.0);
    safetyValve.setFullOpenPressure(82.5);
    safetyValve.setBlowdown(7.0);
    safetyValve.setOutletPressure(1.5, "bara");

    RuptureDisk ruptureDisk = new RuptureDisk("RD-100", feed);
    ruptureDisk.setBurstPressure(85.0);
    ruptureDisk.setFullOpenPressure(89.25);
    ruptureDisk.setOutletPressure(1.5, "bara");

    ESDValve inletIsolation = new ESDValve("ESD-XV-100", feed);
    inletIsolation.setStrokeTime(2.0);
    inletIsolation.setCv(500.0);
    inletIsolation.setOutletPressure(75.0, "bara");
    inletIsolation.setCalculateSteadyState(false);
    inletIsolation.energize();

    BlowdownValve blowdownValve = new BlowdownValve("BDV-100", feed);
    blowdownValve.setOpeningTime(2.0);
    blowdownValve.setCv(100.0);
    blowdownValve.setOutletPressure(1.5, "bara");
    blowdownValve.setCalculateSteadyState(false);

    ESDLogic esdLogic = new ESDLogic("ESD level 1");
    esdLogic.addAction(new TripValveAction(inletIsolation), 0.0);
    esdLogic.addAction(new ActivateBlowdownAction(blowdownValve), 0.0);
    esdLogic.activate();

    UUID calculationId = UUID.randomUUID();
    double timeStepSeconds = 0.5;
    for (int step = 0; step < 20 && !esdLogic.isComplete(); step++) {
      esdLogic.execute(timeStepSeconds);
      inletIsolation.runTransient(timeStepSeconds, calculationId);
      blowdownValve.runTransient(timeStepSeconds, calculationId);
    }

    if (!esdLogic.isComplete()
        || inletIsolation.getPercentValveOpening() > 1.0
        || blowdownValve.getPercentValveOpening() < 90.0
        || Math.abs(safetyValve.getBlowdownPressure() - 69.75) > 1.0e-9
        || ruptureDisk.getBurstPressure() != 85.0) {
      throw new IllegalStateException("Safety-equipment sequence did not complete");
    }

    logger.info(
        "ESD complete: inlet opening {}%, blowdown opening {}%",
        inletIsolation.getPercentValveOpening(),
        blowdownValve.getPercentValveOpening());
  }
}

The regression test src/test/java/neqsim/process/safety/ProcessSafetyOverviewDocumentationTest.java executes this sequence and protects the documented constructors, units, state transitions, and completion criteria.

Transient execution contract

  1. Initialize and run the upstream thermodynamic stream or steady-state process.
  2. Set stateful safety equipment to transient mode where its automatic travel logic is required.
  3. Activate the ESD or HIPPS logic explicitly; construction alone does not trigger it.
  4. Advance logic and equipment using a justified time step and a stable UUID for the calculation.
  5. Capture pressure, temperature, inventory, valve position, relief flow, flare load, MDMT or hydrate margin, and acceptance-criterion results in structured evidence.
  6. Check conservation, numerical convergence, event ordering, time-step sensitivity, and the final safe state before interpreting the scenario.

A valve connected to a stream is not a complete depressuring model. The protected inventory, equipment holdup, heat transfer, flare-header backpressure, downstream equipment, control logic, and scenario boundary conditions must also be represented.

Relief and fire screening boundary

Use Relief-Valve Sizing Screening for the maintained gas, liquid, two-phase, and wetted-fire sizing interfaces. Do not attach an undocumented heat input to an arbitrary vessel or infer an API 526 letter from SafetyValve; the dynamic equipment class does not expose those sizing methods.

Use Integrated Facility Safety Response when relief, blowdown, flare, compressor trip, process limits, MDMT, and hydrate margin must be reviewed as one scenario. Static relief sizing and dynamic transient response answer different questions and should both retain method, unit, input-basis, and qualification metadata.

Safety lifecycle boundary

NeqSim can calculate and retain evidence, but it does not:

Avoid fixed ESD-level meanings or universal depressuring-time targets. Define them in the project basis and trace each acceptance criterion to the applicable controlled source.